26
20306750
Designer Series Direct Vent Gas Fireplace
1
2
3
4
1
2
3
4
FP2309
max elbow use A
Figure 36 -
Maximum Elbow Usage
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation = 270°
INSTALLATION FOR VERTICAL TERMINA-
TION
1. Determine the route your vertical venting will take. If
ceiling joist, roof rafters or other framing will obstruct
the venting system, consider an offset. Refer to
Figure
32
to avoid cutting load bearing members.
NOTE:
Pay special attention to these installation instructions
for required clearances (air space) to combustibles when
passing through ceilings, walls, roofs, enclosures, attic
rafters, etc. Do not pack air spaces with insulation. Also
note maximum vertical rise of the venting system and any
maximum horizontal offset limitations. Offsets must fall
within the parameters shown on
Page 19, Figure 18
.
2. Set fireplace in desired location. Drop a plumb line down
from the ceiling to the position of the flue exit. Mark the
center point where the vent will penetrate the ceiling.
Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locat-
ing hole in the ceiling. Mark the center point where the
vent will penetrate the roof. Drill a small locating hole
at this point.
FP1969
offset w/ wallstrap
Figure 37 -
Offset with Wall Strap and 45° Elbows
Roof
Flashing
Wall Strap
45° Elbows
Ceiling Firstop
FP1669
FLAT CEILING INSTALLATION
1. Cut a 10
1
⁄
2
" (267 mm) square hole in the ceiling using
the locating hole as a center point The opening should
be framed to 10
1
⁄
2
" x 10
1
⁄
2
" (267 x 267 mm) inside
dimensions as shown in
Figure 39
using framing lumber
the same size as the ceiling joist. If the area above the
ceiling is an insulated ceiling or a room, nail firestop
from the top side. This prevents loose insulation from
falling into the required clearance space.
Figure 39.
Otherwise, install firestop below the framed hole. The
firestop should be installed with no less than three (3)
nails per side.
Figure 38 or 39.
2. Assemble the desired lengths of pipe and elbows nec
-
essary to reach from the burner system flue up through
the firestop. Be sure pipe and elbow connections are
fully twist-locked.
Page 20, Figure 20.
3. Cut a hole in the roof using the locating hole as a center
point. (Cover any exposed open vent pipes before
cutting hole in roof). The 10
1
⁄
2
" x 10
1
⁄
2
" (267 x 267 mm)
hole must be measured on the horizontal. Actual length
may be larger depending on the pitch of the roof. There
must be a 1" minimum clearance from the vent pipe to
combustible materials. (Insulation should be considered
a combustible material). Frame the opening as shown
on
Page 20, Figure 21.
4. Connect a section of pipe and extend up through the
hole.
VENTING INSTALLATION