background image

Vermont Castings  •  Apsen C3 Installation Manual_R2  •  2019 - ___ •  07/19

16

8390-950i

Thimble

Site constructed for masonry chimney installation:

Components

• 

A  minimum  length  of  12”  (305  mm)  (longer  for  thicker 

walls)  of  solid  insulated  factory-built  chimney  length 

constructed  to  UL  103  Type  HT  6”  (152  mm)  inside 

diameter. Chimney needs to extend a minimum of 2” (51 

mm) from the interior wall and a minimum of 1” (25 mm) 

from the exterior wall.

• 

Wall  spacer,  trim  collar  and  wall  band  to  fit  solid  pack 

chimney selected.

• 

Minimum 8” (203 mm) diameter clay liner section (if not 

already present in chimney) and refractory mortar.

•  When jurisdiction requires install approved chimney liner 

in masonry chimney.

Air Clearances

•   Masonry  chimney  clearance  must  meet  NFPA  211 

minimum  requirement  of  2”  (51  mm)  to  sheet  metal 

supports and combustibles.

•   Minimum of 1” (25 mm) clearance around the chimney 

connector.

•   Top of wall opening is a minimum of 13-1/2” (343 mm) 

from ceiling or 4-1/2” (114 mm) below minimum clearance 

specified by chimney connector manufacturer. NFPA 211 

minimum vertical clearance of 18” (457mm) from chimney 

connector and ceiling or minimum recommended by 

chimney connector manufacturer. Figure 4.3

Instructions

1.  Open  inside  wall  at  proper  height  for  the  chimney 

connector to enter the masonry chimney. Figure 4.3

2.  Entry hole to masonry chimney must be lined with an 8” 

(203 mm) minimum diameter clay liner, or equivalent, 

secured with refractory mortar.

3.  Construct  a  17”  x  17”  (432  mm  x  432  mm)  outside 

dimension frame from 2 x 2 framing lumber to fit into 

wall opening. Inside opening of frame should be no less 

than 14” x 14” (356 mm x 356 mm). Figure 4.4. 

Attach the wall spacer to the chimney side of the frame.

5.  Nail the frame into the wall opening. The spacer should 

be on the chimney side.

6.  Insert the section of the solid insulated chimney into the 

outer wall of the masonry chimney.

7.  Tightly secure the length of the solid insulated chimney 

with the wall band to the masonry chimney.

8.  Insert a section of chimney connector into the chimney. 

Make sure it does not protrude past the edge of the clay 

chimney liner inside the chimney.

9.  Seal the end of the chimney connector to the clay liner 

with refractory mortar.

10. 

Install trim collar around the sold pack chimney section

.

Solid Pack Chimney with Metal Supports as a Thimble

Trim Collar

Chimney Section 

with 2 inch (51 mm) 

Clearance to 

Combustibles

Chimney 

Connector

Fire Clay Flue Liner

with Airspace

Masonry

 Chimney

Wall Band to 

Secure Chimney 

Section

Wood Studs Used for 

Framing - Spaced 2 

inch (51 mm) clearance 

from Masonry Chimney

Wall Spacer

Figure 4.3

Fire Risk

Do NOT pack insulation or other combustibles 

between spacers.

WARNING

!

•  ALWAYS maintain specified clearances around venting 

and spacers.

•  Install spacers as specified.
Failure to keep insulation or other material away from vent 

pipe may cause fire.

Solid Pack Chimney with Metal Supports as a Thimble 

(Cont’d)

1 inch (35 mm) Air Space 

to Chimney Section 

Min. Clearance 

2 inch (51 mm)

Min. Chimney Clearance to Wall Spacer 

and Combustible - 2 inch (51 mm)

Chimney 

Flue Liner

Fireclay Liner 

or Equivalent

Masonry Chimney 

Constructed to NFPA 211

Wall Spacer

Wall Band

Trim Collar

Chimney Section

Chimney 

Connector

Figure 4.4

Содержание Aspen C3

Страница 1: ...any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends HHT Factory Trained or NFI certified profe...

Страница 2: ...Certification 3 B BTU Efficiency Specifications 3 C Mobile Home Approved USA Canada 3 D Glass Specifications 3 E Non Combustible Materials 4 F Combustible Materials 4 G California Safety Information 4 2 Getting Started A Design Installation Considerations 5 B Fire Safety 5 C Negative Pressure 5 D Tools And Supplies Needed 6 E Inspect Appliance and Components 6 F Install Checklist 7 3 Dimensions an...

Страница 3: ... with 8 copper ground wire and chimney must be listed to UL103 HT or a listed UL 1777 full length six 152mm diameter liner must be used Outside air must be installed in a mobile home installation D Glass Specifications This appliance is equipped with 5mm ceramic glass Replace glass only with 5mm ceramic glass Please contact your dealer for replacement glass EPA Certification Number EPA Certified E...

Страница 4: ...ifornia to cause cancer and carbon monoxide which is know to the State of California to cause birth defects or other reproductive harm For more information go to www P65Warnings ca gov G California Safety Information H Smoke CO Detectors Safety Tips Smoke and CO Detectors The use of smoke and carbon monoxide CO detectors throughout the home is strongly advised even if not required by building code...

Страница 5: ...d be given serious consideration 1 Install at least one smoke detector on each floor of your home to ensure your safety They should be located away from the heating appliance and close to the sleeping areas Follow the smoke detector manufacturer s placement and installation instructions and be sure to maintain regularly 2 Getting Started Check building codes prior to installation Installation MUST...

Страница 6: ...ulking material Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits Plumb line Safety glasses Level Tape measure Misc screws and nails 1 2 3 4 in length 6 or 8 self drilling screws Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and or use of any c...

Страница 7: ...ured in place with proper clearance Chimney meets recommended height requirements 16 Feet Roof flashing installed and sealed Terminations installed and sealed Clearances Combustible materials not installed on non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth strips and hear...

Страница 8: ...ew 15 381 mm 25 1 16 637 mm 16 406 mm 23 1 2 597 mm 24 1 4 616 mm Aspen C3 Specs 01 04 19 ts 24 1 2 623 mm 27 3 16 691 mm 15 381 mm 25 1 16 637 mm 16 406 mm 23 1 2 597 mm 24 1 4 616 mm 6 1 4 159 mm 7 1 2 191 mm Aspen C3 Specs 01 04 19 ts 24 1 2 623 mm 27 3 16 691 mm Figure 3 2 Side View 25 1 16 637 mm 23 1 2 597 mm 24 1 4 616 mm 6 1 4 159 mm 7 1 2 191 mm Aspen C3 Specs 01 04 19 ts 24 1 2 623 mm 27...

Страница 9: ...ear A Figure 3 4 Figure 3 5 Supporting timbers under fireplace hearths are considered to be combustible Comb Floor Dia 01 07 19 ts Wood framing requires protection from radiant heat Fireplace Hearth Protection For all fireplace installations follow the floor protection guidelines described above Keep in mind that many raised hearths will extend less than the required clearance from the front of th...

Страница 10: ...m B Back Wall to Appliance 3 76 mm C Side Wall to Vent Pipe 18 457 mm D Back Wall to Vent Pipe 5 1 2 140 mm Vertical Vent Horizontal Exit Description Single Wall Pipe A Side Wall to Appliance 14 356 mm B Back Wall to Appliance 8 203 mm C Side Wall to Vent Pipe 18 1 2 470 mm D Back Wall to Vent Pipe 11 279 mm E Minimum Vertical 0 0 mm F Minimum Floor to Ceiling 84 2134 mm G Minimum Vent Pipe to Cei...

Страница 11: ... clearances Fireplace Clearances A fireplace installation requires special clearance between the side of the stove and the right and left walls the side of the stove and the decorative side trim on the fireplace face and the top of the stove and the mantel Maximum Mantel depth A Figure 3 10 of a combustible mantel is 9 230 mm At that depth the clearance to the stove top B must be a minimum of 22 1...

Страница 12: ... should Install through the warm space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind turbulence and down drafts NOTICE Locating the appliance in a basement or in a location of considerable air movement can cause intermittent smoke spillage from applianc...

Страница 13: ... diameter of the chimney can affect draft and cause poor performance It is not recommended to use offsets and elbows at altitudes above 4000 feet above sea level and or when there are other factors that affect flue draft 3 ft 91 cm Minimum Less than 10 ft 305 cm 2 ft 61 cm 3 ft 91 cm Minimum 10 ft 305 cm To Nearest Roofline 2 ft 61 cm Pitched Roof Figure 3 13 10 ft 305 cm or more 3 ft 91 cm Minimu...

Страница 14: ...keep it warm Single Venting Each airtight stove requires its own flue If an airtight stove is vented to a flue that also serves an open fireplace or a leakier stove it s easier for the chimney draft to pull air in through those channels and performance of the stove suffers Imagine a vacuum cleaner with a hole in the hose to understandtheeffecthere Insomecasestheotherappliance can even cause a nega...

Страница 15: ... chimney can be new or existing masonry or prefabricated and must meet the following minimum requirements specified in section 4C Chimney Systems C Chimney Systems Prefabricated Metal Chimney Must be minimum 6 152 mm diameter ID high temperature chimney listed to UL 103 HT 2100 F or ULC S629M Must use components required by the manufacturer for installation Must maintain clearances required by the...

Страница 16: ...framing lumber to fit into wall opening Inside opening of frame should be no less than 14 x 14 356 mm x 356 mm Figure 4 4 Attach the wall spacer to the chimney side of the frame 5 Nail the frame into the wall opening The spacer should be on the chimney side 6 Insert the section of the solid insulated chimney into the outer wall of the masonry chimney 7 Tightly secure the length of the solid insula...

Страница 17: ...ion consult a qualified installer service agency or your dealer WARNING Flue Gas Direction Crimped End Toward Appliance Secure pipe sections with a minimum of 3 screws Figure 4 7 Chimney Connector Appliance Pipe Fire Risk Follow Chimney Connector Manufacturer s Instructions for Proper Installation ONLY use connector WARNING Within the room between appliance and ceiling or wall Connector shall NOT ...

Страница 18: ... the remaining two legs with hex bolts and washers 5 Appliance Set Up Carefully tilt the stove on the shipping brackets to install one front and one rear leg Then tilt the stove up on those legs to install the remaining two Figure 5 1 Install legs on one side of stove then the other Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by...

Страница 19: ...UCH AS AN ATTIC OR GARAGE CAUTION 2 The stove must have a permanent connection to the outside to supply combustion air 3 A listed chimney system including roof thimble spark arrestor chimney supports roof flashing and any other components suitable for use in mobile homes must be used The chimney system must comply with the standard for Chimneys Factory Built Residential Type and Building Heating A...

Страница 20: ...nt operating and maintenance instructions included Leave this manual with party responsible for use and operation Read understand and followtheseinstructions for safe installation and operation DO NOT DISCARD This product may be covered by one or more of the following patents United States 5341794 5263471 6688302 7216645 7047962 or other U S and foreign patents pending We recommend that you record...

Отзывы: