E. Chimney Termination Requirements

Follow manufacturer’s instructions for clearance, securing 

flashing and terminating the chimney. Figures 3.13 & 3.14.
•  Must have an approved and Listed cap

•  Must not be located where it will become plugged by 

snow or other material

•  Must  terminate  at  least  3  feet  (91  cm)  above  the  roof 

and

 at least 2 feet (61 cm) above any portion of the roof 

within 10 feet (305 cm).

•  Must be located away from trees or other structures

NOTICE:

•  Chimney performance may vary.
•  Trees, buildings, roof lines and wind conditions affect 

performance.

•  Chimney  height  may  need  adjustment  if  smoking  or 

overdraft occurs.

D. Locating Your Appliance & Chimney

Location  of  the  appliance  and  chimney  will  affect 

performance. As shown in Figure 3.12 the chimney should:

•  Install through the warm space enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die down of the fire.

•  Penetrate the highest part of the roof. This minimizes the 

affects of wind turbulence and down drafts.

NOTICE: 

Locating  the  appliance  in  a  basement  or  in  a 

location of considerable air movement can cause intermittent 

smoke spillage from appliance. Do not locate appliance near

•  Frequently open doors
•  Central heat outlets or returns

•  Consider  the  appliance  location  in  order  to  avoid  floor 

and ceiling attic joists and rafters.

• 

Locate  termination  cap  away  from  trees,  adjacent 

structures, uneven roof lines and other obstructions.

Your local dealer is the expert in your geographic area and 

can usually make suggestions or discover solutions that will 

easily correct your flue problem.

Figure 3.12

Recommended 

Location

Marginal

Location

Location

Not

Recommended

 

Recommended

Location

 

Location NOT 

Recommended

Multi-level Roofs

Windward

Leeward

Outside Air Kit Termination Cap

Содержание Aspen C3

Страница 1: ...any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends HHT Factory Trained or NFI certified profe...

Страница 2: ...Certification 3 B BTU Efficiency Specifications 3 C Mobile Home Approved USA Canada 3 D Glass Specifications 3 E Non Combustible Materials 4 F Combustible Materials 4 G California Safety Information 4 2 Getting Started A Design Installation Considerations 5 B Fire Safety 5 C Negative Pressure 5 D Tools And Supplies Needed 6 E Inspect Appliance and Components 6 F Install Checklist 7 3 Dimensions an...

Страница 3: ... with 8 copper ground wire and chimney must be listed to UL103 HT or a listed UL 1777 full length six 152mm diameter liner must be used Outside air must be installed in a mobile home installation D Glass Specifications This appliance is equipped with 5mm ceramic glass Replace glass only with 5mm ceramic glass Please contact your dealer for replacement glass EPA Certification Number EPA Certified E...

Страница 4: ...ifornia to cause cancer and carbon monoxide which is know to the State of California to cause birth defects or other reproductive harm For more information go to www P65Warnings ca gov G California Safety Information H Smoke CO Detectors Safety Tips Smoke and CO Detectors The use of smoke and carbon monoxide CO detectors throughout the home is strongly advised even if not required by building code...

Страница 5: ...d be given serious consideration 1 Install at least one smoke detector on each floor of your home to ensure your safety They should be located away from the heating appliance and close to the sleeping areas Follow the smoke detector manufacturer s placement and installation instructions and be sure to maintain regularly 2 Getting Started Check building codes prior to installation Installation MUST...

Страница 6: ...ulking material Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits Plumb line Safety glasses Level Tape measure Misc screws and nails 1 2 3 4 in length 6 or 8 self drilling screws Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and or use of any c...

Страница 7: ...ured in place with proper clearance Chimney meets recommended height requirements 16 Feet Roof flashing installed and sealed Terminations installed and sealed Clearances Combustible materials not installed on non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth strips and hear...

Страница 8: ...ew 15 381 mm 25 1 16 637 mm 16 406 mm 23 1 2 597 mm 24 1 4 616 mm Aspen C3 Specs 01 04 19 ts 24 1 2 623 mm 27 3 16 691 mm 15 381 mm 25 1 16 637 mm 16 406 mm 23 1 2 597 mm 24 1 4 616 mm 6 1 4 159 mm 7 1 2 191 mm Aspen C3 Specs 01 04 19 ts 24 1 2 623 mm 27 3 16 691 mm Figure 3 2 Side View 25 1 16 637 mm 23 1 2 597 mm 24 1 4 616 mm 6 1 4 159 mm 7 1 2 191 mm Aspen C3 Specs 01 04 19 ts 24 1 2 623 mm 27...

Страница 9: ...ear A Figure 3 4 Figure 3 5 Supporting timbers under fireplace hearths are considered to be combustible Comb Floor Dia 01 07 19 ts Wood framing requires protection from radiant heat Fireplace Hearth Protection For all fireplace installations follow the floor protection guidelines described above Keep in mind that many raised hearths will extend less than the required clearance from the front of th...

Страница 10: ...m B Back Wall to Appliance 3 76 mm C Side Wall to Vent Pipe 18 457 mm D Back Wall to Vent Pipe 5 1 2 140 mm Vertical Vent Horizontal Exit Description Single Wall Pipe A Side Wall to Appliance 14 356 mm B Back Wall to Appliance 8 203 mm C Side Wall to Vent Pipe 18 1 2 470 mm D Back Wall to Vent Pipe 11 279 mm E Minimum Vertical 0 0 mm F Minimum Floor to Ceiling 84 2134 mm G Minimum Vent Pipe to Cei...

Страница 11: ... clearances Fireplace Clearances A fireplace installation requires special clearance between the side of the stove and the right and left walls the side of the stove and the decorative side trim on the fireplace face and the top of the stove and the mantel Maximum Mantel depth A Figure 3 10 of a combustible mantel is 9 230 mm At that depth the clearance to the stove top B must be a minimum of 22 1...

Страница 12: ... should Install through the warm space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind turbulence and down drafts NOTICE Locating the appliance in a basement or in a location of considerable air movement can cause intermittent smoke spillage from applianc...

Страница 13: ... diameter of the chimney can affect draft and cause poor performance It is not recommended to use offsets and elbows at altitudes above 4000 feet above sea level and or when there are other factors that affect flue draft 3 ft 91 cm Minimum Less than 10 ft 305 cm 2 ft 61 cm 3 ft 91 cm Minimum 10 ft 305 cm To Nearest Roofline 2 ft 61 cm Pitched Roof Figure 3 13 10 ft 305 cm or more 3 ft 91 cm Minimu...

Страница 14: ...keep it warm Single Venting Each airtight stove requires its own flue If an airtight stove is vented to a flue that also serves an open fireplace or a leakier stove it s easier for the chimney draft to pull air in through those channels and performance of the stove suffers Imagine a vacuum cleaner with a hole in the hose to understandtheeffecthere Insomecasestheotherappliance can even cause a nega...

Страница 15: ... chimney can be new or existing masonry or prefabricated and must meet the following minimum requirements specified in section 4C Chimney Systems C Chimney Systems Prefabricated Metal Chimney Must be minimum 6 152 mm diameter ID high temperature chimney listed to UL 103 HT 2100 F or ULC S629M Must use components required by the manufacturer for installation Must maintain clearances required by the...

Страница 16: ...framing lumber to fit into wall opening Inside opening of frame should be no less than 14 x 14 356 mm x 356 mm Figure 4 4 Attach the wall spacer to the chimney side of the frame 5 Nail the frame into the wall opening The spacer should be on the chimney side 6 Insert the section of the solid insulated chimney into the outer wall of the masonry chimney 7 Tightly secure the length of the solid insula...

Страница 17: ...ion consult a qualified installer service agency or your dealer WARNING Flue Gas Direction Crimped End Toward Appliance Secure pipe sections with a minimum of 3 screws Figure 4 7 Chimney Connector Appliance Pipe Fire Risk Follow Chimney Connector Manufacturer s Instructions for Proper Installation ONLY use connector WARNING Within the room between appliance and ceiling or wall Connector shall NOT ...

Страница 18: ... the remaining two legs with hex bolts and washers 5 Appliance Set Up Carefully tilt the stove on the shipping brackets to install one front and one rear leg Then tilt the stove up on those legs to install the remaining two Figure 5 1 Install legs on one side of stove then the other Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by...

Страница 19: ...UCH AS AN ATTIC OR GARAGE CAUTION 2 The stove must have a permanent connection to the outside to supply combustion air 3 A listed chimney system including roof thimble spark arrestor chimney supports roof flashing and any other components suitable for use in mobile homes must be used The chimney system must comply with the standard for Chimneys Factory Built Residential Type and Building Heating A...

Страница 20: ...nt operating and maintenance instructions included Leave this manual with party responsible for use and operation Read understand and followtheseinstructions for safe installation and operation DO NOT DISCARD This product may be covered by one or more of the following patents United States 5341794 5263471 6688302 7216645 7047962 or other U S and foreign patents pending We recommend that you record...

Отзывы: