IO Controller

Install Guide

Содержание AX11

Страница 1: ...Verkada Inc 405 E 4th Ave San Mateo CA 94401 sales verkada com All specifications are subject to change without notice Copyright Verkada Inc All rights reserved AX11 IO Controller Install Guide ...

Страница 2: ...ce pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this...

Страница 3: ...meter to confirm expected impedance across relay outputs Short across NC and COM Open across NO and COM Use multimeter to verify aux voltage is supplied at 12V outputs Solid Orange Controller is on and booting up Flashing Orange Controller is updating firmware Flashing Blue Controller is managing inputs and outputs but cannot reach the server Solid Blue Controller is managing inputs and outputs an...

Страница 4: ...ominal 5VDC Relay Outputs 16 Dry Relays 1A 24VDC Contacts AUX Power 2 External Outputs 1A 12V Power Each 2A Combined Max Dimensions With Mount 415 6mm L x 319 6mm W x 111 74 H Without Mount 415 6mm L x 319 6mm W x 105 74 H Weight 8 3kg Operating Temperature 00C 500C 5 90 Humidity Compliance FCC CE Connectivity Ethernet 100 1000Mbps RJ 45 cable connector for network connection USB 2 0 Included Acce...

Страница 5: ...e subject to change without notice Copyright Verkada Inc All rights reserved To remove the mounting plate unscrew the two security torx screws from the inside Once the security screws are fully removed slide the mounting plate down and away from the main enclosure Mounting Installation ...

Страница 6: ...hors into the holes Fasten the mounting plate onto the wall by installing the mounting screws into the wall anchors Drill four 5 32 Ø holes into the wall Fasten the mounting plate onto the wall by installing the mounting screws into the pilot holes Place the sheet metal enclosure over and onto the mounting plate tabs Fasten the two security torx screws to secure the enclosure to the mounting plate...

Страница 7: ...ing Verkada Readers over RS 485 and standard Wiegand readers The following table shows the wire types that are recommended for use with AX11 We recommend using one twisted pair for GND and Vin power and one twisted pair for the data D0 D1 or A B Wiring methods shall be in accordance with National Electrical Code ANSI NFPA 70 Required Network Settings With the AX11 you must use shield wiring Drain ...

Страница 8: ...ervision resistors 12V Power 12V Output terminals support up to 2A combined max Battery Backup Battery should be sized to provide at least 4 hours of operation The AX11 consumes 8 6W with no load i e no inputs outputs or readers connected AC Field Wiring If AC power is brought in via conduit cut and splice wire going from AC inlet to PSU Inputs AX11 has 16 Dry Contact Inputs Nominal 5VDC Line resi...

Страница 9: ...ay Fail Secure Fail Safe Depending on your APC and lock your configuration may vary from the above Ensure power is disconnected from the AX11 before plugging in or unplugging any of the terminal blocks Failure to do so may damage the AX11 Warning Access Power Controller AX11 Relay Output IN Input Output GND NC COM NO Lock Access Power Controller AX11 Relay Output IN Input Output GND NC COM NO Lock...

Страница 10: ...GND connection The drain wire of the shielded cable should be secured to nearest AX11 chassis ground Verkada Reader Wiegand Reader Wire Color Signal Red 12V Power Black 12V Power Purple A Blue B Wire Color Signal Red 12V Power Black 12V Power Green Data 0 White Gray Data 1 Brown Red LED Orange Green LED Shielded Cable AX11 RS 485 Verkada Reader A B Shielded Cable Wiegand Reader AX11 Wiegand D0 D1 ...

Страница 11: ...m of the AX11 We recommend and sell a 12 Volt 4 5 Ah Sealed Lead Acid Rechargeable battery If you are using two batteries ensure they are wired in parallel Connect Connect the AX11 to your network using either of the Ethernet ports located at the bottom of the controller If you are installing multiple controllers you can connect up to 4 additional controllers via the spare Ethernet port on each co...