background image

Z207937-0E 

Page 1 of 8 

©2021 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0421 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  Read and understand the instructions before installing this product.

•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

Installation Guide

Temperature

Product Identification

Product Overview

The TW2 Series of temperature sensors for living space is a versatile sensor platform for use with BAS controllers 
designed to accept 4 to 20mA, 0 to 5Vdc or 0 to 10Vdc outputs. TW2 Series sensors are available with three user 
interface options: touchscreen, LCD with three buttons and blank. 

TW2 Series

Wall Mount Temperature Sensors

Specifications

OPERATING ENVIRONMENT

Input Power

Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz

Analog Output

Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V

Operating Temp. Range

0 to 50 °C (32 to 122 °F)

Operating Humidity Range

0 to 95% RH non-condensing

Housing Material

High-impact ABS plastic

Terminal Block Torque

0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)

IP Rating

IP 30

TEMPERATURE TRANSMITTER OPTION

Sensor Type

Solid state, integrated circuit

Accuracy

±0.2 °C (±0.4 °F) typical

Resolution

0.1 °C (0.1 °F)

Range

0 to 50 °C (32 to 122 °F)

DISPLAY MODELS

Touchscreen

61 mm (2.4 in), color, backlit, capacitive, 240x300 px 
Setpoint: 0-10Vdc. Temperature or fan speed selectable 
Timeout override: Display timeout* 
Lockout override: Touchscreen/button lockout*

LCD

52mm (2.05 in), segmented with 3 buttons 
Setpoint: 0-10Vdc. Temperature or fan speed selectable 
Timeout override: Display timeout* 
Lockout override: Touchscreen/button lockout*

TW2

User Interface

Output

Temperature

T  = Color touchscreen
L  = 3-button LCD display
X  = None

A  = Analog output

A  = Transmitter only
C  = 1000 PT RTD
D  = 10K T2 thermistor
H  = 10K T3 thermistor
K  = 10K curve G/11K shunt
M  = 20K NTC thermistor
N  = 1.8K TAC thermistor

TW2TAXx

TW2LAXx

TW2XAXx

X

Содержание TW2 Protocol Series

Страница 1: ...designed to accept 4 to 20mA 0 to 5Vdc or 0 to 10Vdc outputs TW2 Series sensors are available with three user interface options touchscreen LCD with three buttons and blank TW2 Series Wall Mount Temperature Sensors Specifications OPERATING ENVIRONMENT Input Power Class2 20to30Vdc 24Vac 50to60Hz Analog Output Selectable4to20mA 0to5V 0to10V Operating Temp Range 0to50 C 32to122 F Operating Humidity R...

Страница 2: ...w3 3V Med 6 7V High10 0V WIRING TERMINALS Terminal Blocks Screwterminals 18 24AWG Screw Terminal Torque 0 2N m 2 0in lbF max OVERRIDE Override Button Displaymodelsfeatureamomentary to groundoverridebutton WARRANTY Limited Warranty 5years COMPLIANCE INFORMATION Agency Approvals UL916 EuropeanconformanceCE EN61000 6 2 EN61000 6 3 EN61000Series industrialimmunity EN61326 1 FCCPart15ClassB REACH RoHS ...

Страница 3: ...rom windows vents and other sources of draft If possible do not mount on an external wall as this may cause inaccurate temperature readings 3 Pull 18 or 22 AWG cable s through the hole in the backplate 4 Mount the backplate onto the wall using the screws provided Six screw holes available Use a minimum of two for secure mounting Connect the wires to the screw terminals Do not over tighten the scre...

Страница 4: ...with RTD thermistor 10 9 8 7 6 5 4 3 2 1 OVERRIDE SETPOINT OUT RTD THERMISTOR OUT RTD THERMISTOR OUT POWER SUPPLY 20 30Vdc 24Vac CONTROL SYSTEM COMMON COMMON POWER 24 Momentarytoground 0 10VDIPswitchselectablefortemperature RHorfanspeed off 0V Low3 3V Medium6 7Vorhigh10V Set the DIP switches ON 1 2 3 4 5 6 7 8 Temp Fan Setpoint Temp Range 1 2 Screen Timeout On Off Touch Button Disable On Off mA Vo...

Страница 5: ...s and buttons are disabled ON Touchscreen touch button functions disabled OFF Touchscreen touch button functions enabled Onlyusedwithvoltageoutputmodeenabled Notapplicabletosetpointoutput Setpointis0 10Vfixed 5 With sensor base fully installed align top of cover to mounting tabs on top of sensor base Swing cover downward until it latches at the bottom 6 Install locking screw to secure cover in clo...

Страница 6: ...d Set by DIP switch Submenu Only Submenu Only Settings This icon provides the ability to change the color scheme of the display Temp Setpoint Adjustment Click this icon to access the setpoint change menu Mutually exclusive with fan speed set by DIP switch Integrator s Submenu Press this icon to access the Integrator s menu Submenu Only Occupied Override Button Press this icon to provide momentary ...

Страница 7: ...s sensor values for temperature and Celsius Fahrenheit A single 0 10V setpoint temperature or fan speed can be selected via DIP switch TemperatureSetpointAdjustment ChangeValues Menu Advance ChangeValues Temperature Value Override Press Indicator Adjusts setpoint up Adjusts setpoint down et mode Press the Menu Advance button After adjustment wait 6 seconds or press the Menu Advance button Setpoint...

Страница 8: ...ration of hazardous substance in all of the homogeneousmaterials for this part is below the limit as stipulated in GB T 26572 X indicates that concentration of hazardous substance in at least one of the homogeneous X O O O O O materials used for this part is above the limit as stipulated in GB T 26572 Z000057 0B 部件名称 Part Name 有害物质 Hazardous Substances 铅 Pb 汞 Hg 镉 Cd 六价铬 Cr VI 多溴联苯 PBB 多溴二苯醚 PBDE ...

Отзывы: