Installation Guide

Power Metering CTs

TM

DR

AF

T

Product Identification

Product

Description

E683D502

Rogowski CT, 300 mm (12”), 600 Vac, 5 kA

E683G502

Rogowski CT, 460 mm (18”), 600 Vac, 5 kA

E683J502

Rogowski CT, 600 mm (24”), 600 Vac, 5 kA

E683L502

Rogowski CT, 900 mm (36”),  600 Vac, 5 kA

Product Overview

The E683x Series of Rogowski flexible rope style current transducers (CTs) provide secondary AC voltage 
proportional to the primary (sensed) current. For use with E5xxxA and E2x Series power meters, the E683x 
Series CTs provide a cost-effective means to transform electrical service amperages to a voltage compatible 
with monitoring equipment. The flexible core makes it easy to fit in tight enclosures.

These products provide reinforced insulation between the sensed conductor and the output leads. 

E683x Series

Rogowski Current Transducers 

for use with E5xxxA & E2x Series Power Meters

Specifications

Output at Rated Current

Custom for E5xxxA and E2x Series power meters

Accuracy

±1% from 50 to 5000 A

Frequency Range

50/60 Hz

Cable

1000 Vac UL Style 21223 cable with 22 AWG leads

Operating Temperature Range

-15 to +60 °C (+5 to +140 °F)

Storage Temperature Range

-40 to +70 °C (-40 to +158 °F)

Humidity Range

0 to 95% non-condensing

Max. Voltage L-N Sensed Conductor

600 Vac (reinforced insulation rating) 

Altitude of Operation

2000 m max.

COMPLIANCE INFORMATION

Approvals

EN61010-1; UL61010-1; EN61010-2-032; UL61010-2-032;  

CAN/CSA-C22.2 No. 61010-1

Installation Category

600 Vac Cat IV, Pollution Degree 2

WARRANTY

Limited Warranty

3 years

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Do not use this product for life or safety applications.
•  Do not install this product in hazardous or classified locations.
•  Mount this product inside a suitable fire and electrical enclosure.
•  Apply appropriate personal protective equipment (PPE) and follow safe electrical 

work practices. See NFPA 70E in the USA, CSA Z462 or applicable local standards.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Product may use multiple voltage/power sources. Disconnect all sources before

 servicing.
•  Use a properly rated voltage sensing device to confirm that power is off. Do not 

depend on this product for voltage indication.

•  Current transformer secondaries must be shorted or connected to a burden at all times.
•  Replace all doors, covers and protective devices before powering the equipment.

Failure to follow these instructions will result in death or serious injury.

Electrical equipment should be installed, operated, serviced and maintained only by 

qualified personnel. No responsibility is assumed by Veris Industries for any 

consequences arising out of the use of this material. A qualified person is one who has 

skills and knowledge related to the construction, installation and operation of 

electrical equipment and has received safety training to recognize and avoid the 

hazards involved.

Installation, wiring, testing and service must be performed in accordance with all local 

and national electrical codes.

If this product is be used in a manner not specified by the manufacturer, the 

protection provided by the product may be impaired.

DANGER

Do not apply current transducers to circuits that have a phase-to-phase voltage greater
than their voltage rating unless adequate additional insulation is applied between the
primary conductor and the current transducers. Veris assumes no responsibility for 
damage of equipment or personal injury caused by products operated on circuits
above their published ratings.

WARNING