CWV2 Installation Guide

4.   Mount the backplate onto the wall using the screws provided. 

 

 

Six screw holes available. Use a minimum of 
two for secure mounting.

  Connect the wires to the screw terminals. Do not over-tighten the screws. 

 

 

CWV2 wiring diagram: 

 

5 4 3 2 1

COMMON

CO

2

 OUT

POWER (+24)

5.  Set the DIP switches. 

 

ON

1

2

3

4

5

6

7

8

mA / Voltag

e

5V / 10

V

ABC On / Of

f

Unused

Unused

Unused

Unused

Unused

 

 

Installation (cont.)

Содержание CWV2

Страница 1: ...ving space is for use with BAS controllers designed to accept 4 to 20mA 0 to 5 Vdc or 0 to 10 Vdc outputs This sensor measures CO2 levels using a dual beam non dispersive infrared NDIR technology The CWV2 Value sensor with an accuracy of 40 ppm 5 5 of measured value is ideal for bid spec applications CWV2 Value Wall Mounted Air Quality Sensor Specifications OPERATING ENVIRONMENT Input Power Class2...

Страница 2: ...ion Guide Dimensions Functions 115 4 5 85 3 3 24 0 9 The CWV2 sensor measures CO2 and temperature if equipped in a room and provides analog outputs to a controller 1 Remove the cover from the base at the bottom of the device 2 Position the sensor base vertically on the wall 1 35 m 4 5 ft above the floor with the UP arrow facing upward Locate away from windows vents and other sources of draft If po...

Страница 3: ...rcompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners CWV2 Installation Guide 4 Mount the backplate onto the wall using the screws provided Six screw holes available Use a minimum of two for secure mounting Connect the wires to the screw terminals Do not over tighten the screws CWV2 wiring diagram 5 4 3 2 1 COMMON CO2 OUT POWER 24 5 Set the DIP switches ON 1 2 3 4 5 6 7 8 mA Vo...

Страница 4: ...usedwithvoltageoutputmodeenabled 6 With sensor base fully installed align top of cover to mounting tabs on top of sensor base Swing cover downward until it latches at the bottom 7 Install locking screw to secure cover in closed position China RoHS Compliance Information 本表格依据SJ T11364的规定编制 O 表示该有害物质在该部件所有均质材料中的含量均在GB T 26572规定的限量要求以下 X 表示该有害物质至少在该部件的某一均质材料中的含量超出GB T 26572规定的限量要求 企业可在此处 根据实际情况对上表中打...

Отзывы: