CWV2 Installation Guide
Dimensions
Functions
115
(4.5)
85
(3.3)
24
(0.9)
The CWV2 sensor measures CO2 and temperature (if equipped) in a room and provides analog outputs to a controller.
1. Remove the cover from the base at the bottom of the device.
2. Position the sensor base vertically on the wall 1.35 m (4.5 ft.) above the floor with the “UP” arrow facing upward. Locate away
from windows, vents and other sources of draft. If possible, do not mount on an external wall, as this may cause inaccurate
temperature readings.
3. Pull 18 or 22 AWG cable(s) through the hole in the backplate.
Installation