CWE2 Series Installation Guide
Installation (cont.)
5. Set the DIP switches.
ON
1
2
3
4
5
6
7
8
mA / Voltag
e
5V / 10
V
ABC On / Of
f
Unused
Unused
Unused
Unused
Unused
Switch
Function
Description
1
Output mode
ON - 4-20mA output mode enabled
OFF - Voltage output mode enabled
2
Voltage output range*
ON - 0-5V output range enabled
OFF 0-10V output range enabled
3
Automatic Baseline Calibration (ABC)
for CO2
ON - ABC enabled
OFF - ABC disabled
4
Unused
Unused
5
Unused
Unused
6
Unused
Unused
7
Unused
Unused
8
Unused
Unused
* Only used with voltage output mode enabled.
6. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it
latches at the bottom.
7. Install locking screw to secure cover in closed position.