CWE2 Series Installation Guide

Installation (cont.)

5.  Set the DIP switches. 

 

ON

1

2

3

4

5

6

7

8

mA / Voltag

e

5V / 10

V

ABC On / Of

f

Unused

Unused

Unused

Unused

Unused

 

 

Switch

Function

Description

1

Output mode

ON - 4-20mA output mode enabled
OFF - Voltage output mode enabled

2

Voltage output range*

ON - 0-5V output range enabled
OFF 0-10V output range enabled

3

Automatic Baseline Calibration (ABC) 

for CO2

ON - ABC enabled 
OFF - ABC disabled

4

Unused

Unused

5

Unused

Unused

6

Unused

Unused

7

Unused

Unused

8

Unused

Unused

* Only used with voltage output mode enabled.

6.  With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it 

latches at the bottom. 

 

7.  Install locking screw to secure cover in closed position. 

 