Solid-Core Current Switch, Adjustable Output, 

with Command Relay

Installer’s Specifications

Sensor Power 

Induced from monitored current

Insulation Class 

600VAC rms (UL)

Frequency Range 

50/60Hz

Relay Coil 

24VAC/DC 10mA

Relay Contact 

5A@250VAC/DC, 3A@30VDC, 1/6 hp

Temperature Range 

-15° to 60°C (5° to 140°F)

Humidity Range 

10-90% RH non-condensing

Amperage Range 

1-135A continuous

Output  

N.O. 0.1A@30VAC/DC, polarity insensitive

Hysteresis 

10% of setpoint, typical

Off-State Leakage 

1+ MΩ

Safety 

UL 508, CAT III

Do not use the LED status indicators as evidence of applied voltage.

The product design provides for basic insulation only. 

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. 

See NFPA 70E in the USA, or applicable local codes.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Use a properly rated voltage sensing device to confirm power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
•  Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

Wiring ExamplE

H735

TM

735

DimEnsions

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

quick install

Disconnect and lock out power.

1.  

Install the mounting bracket to the back of the electrical enclosure, no closer than 

2.  

1/2” (12mm) to an uninsulated conductor. 

Slide the conductor to be monitored through the sensing hole of the current 

3.  

switch. Terminate the conductor. See Notes (page 2) for currents under 1 Amp or 
above 135 Amps.

Wire the output connections to the DDC controller or switched load. Note:  

4.  

Contacts are solid state and work like dry contacts. When the switch is closed, less 
than 1 Ω is present. When the switch is open, more than 1 MΩ are present.

Reconnect power.

5.  

Calibrate the sensor (see Calibration section).

6.  

0.2” x 0.15”

slot (2x)

1.1" 

(27 mm)

2.8"

(68 mm)

0.7" Dia

(19 mm)

0.9"

(23 mm)

3.0" 

(75 mm)

Removable/Adjustable Mounting Bracket

3.8"

(95 mm)

4.2"

(106 mm)

Fan or Pump

CONTROLLER

DI 

(Status)

DO 

(Relay

          Coil)

Motor

CONTACTOR

CONTROL

POWER

Cross Reference RA Part Number PN-337175