10.0
Fuses and Power Settings
10.1
Fuses
F1 - F3: Refer to the circuit diagrams.
F1
Internal
Supply
Fuses
Fitted if supply cable fitted.
Fitted on board to some types
of EMC filter.
GEC Safeclip of the type shown
(glass type F up to 16 A)
38 mm x 10 mm type F fitted on
EMC filter circuit board(s)
F2
Auxiliary
Circuit Fuses
Fitted on board to some types
of EMC filter.
May be omitted up to 25 Amp/
phase supply rating.
2 Amps glass type F
On board: 20 mm x 5 mm
Other: 32 mm x 6 mm
F3
Heat Light
Fuses
May be omitted up to 25 Amp/
phase supply rating.
2 Amps glass type F
32 mm x 6 mm
Customer
Fuses
Required if no supply cable
fitted.
Recommended if cable fitted.
See rating label for current;
See table below for fuse rating.
Model
Phases
Volts
Supply Fuse Rating
CWF -/23
1-phase
220-240 V
32 A
CWF -/23
3-phase + N
380/220 - 415/240 V
12 A/ ph
CWF -/23
3-phase delta
220-240 V
20 A
10.2
Power Settings
The power limit settings (parameter OP.Hi) for this model are voltage dependant. The
figures represent the maximum percentage of time that controlled power is supplied to
the elements. Do not attempt to “improve performance” by setting a value higher than
the recommended values. To adjust the parameter refer to the "Changing the
Maximum Output Power" of the control section of the manual.
Voltage:
200 V
208 V
110 V
220 V
380 V
115 V
230 V
400 V
120 V
240 V
415 V
254 V
440 V
460 V
480 V
Power (%)
-
-
100
100
94
89
81
75
Please refer to the rating label for product specific information.
33