9.0
Fuses and Power Settings
9.1
Fuses
F1 - F3: Refer to the circuit diagrams.
F1
Internal
Supply
Fuses
Fitted if supply cable fitted.
Fitted on board to some types
of EMC filter.
38 mm x 10 mm type F fitted on
EMC filter circuit board(s)
F2
Auxiliary
Circuit Fuses
Fitted on board to some types
of EMC filter.
May be omitted up to 25 Amp/
phase supply rating.
2 Amps glass type F
On board: 20 mm x 5 mm
Other: 32 mm x 6 mm
F3
Heat Light
Fuses
May be omitted up to 25 Amp/
phase supply rating.
2 Amps glass type F
32 mm x 6 mm
Customer
Fuses
Required if no supply cable
fitted.
Recommended if cable fitted.
See rating label for current;
See table below for fuse rating.
Model
Phases
Volts
Supply Fuse Rating
CRF/1
1-phase
110-120
TBC
CRF/1
1-phase
200-240
6A
9.2
Power Settings
The power limit settings (parameter OP.Hi) for this model are voltage dependant. The
figures represent the maximum percentage of time that controlled power is supplied to
the elements. Do not attempt to “improve performance” by setting a value higher than
the recommended values. To adjust the parameter refer to the "Changing the Maximum
Output Power" of the control section of the manual.
Volts
120 V
208 V
220 V
230 V
240 V
Power (%)
-
-
100
100
-
Please refer to the rating label for product specific information.