Maintenance operations of the unit are required 3-4 times per year.  This includes checking for visible damages and faults, regular cleaning 
and the following operations:

1. Filter maintenance (3-4 times per year).

Dirty filters increase air resistance in the system and reduce supply air volume.  The filters require cleaning not less than 3-4 times per year.  
Vacuum cleaning is allowed.  After two consecutive cleanings filters must be replaced.  For new filters contact the Seller of the unit.  The 
steps to replace the filters are as follows (refer to the figure on p. 21):
1. Press out on the latches.
2. Open the unit panel.
3. Remove the filters from the unit.

2. Fan maintenance (once a year).

Even in case of regular maintenance of the filters, some dust may accumulate inside the fans and reduce the fan performance and supply 
air flow. Clean the fans with a soft brush or cloth.  Do not use water, aggressive solvents, or sharp objects as they may damage the impeller.

3. Heat exchanger maintenance (once a year).

Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the filters.  To maintain the high heat 
recovery efficiency, regular cleaning is required.  To clean the heat exchanger pull it out, flush the heat exchanger with warm detergent 
solution. After cleaning install the dry heat exchanger back to the unit. To remove the filters and the heat exchanger follow the operations 
described in Fig. 19:
1. Release the latches and remove the bottom panel.
2. Open the unit panel.
3. Remove the heat exchanger.

4. Technical maintenance of condensate drainage system (four times a year).

The condensate drainage (drain line) may get clogged by dirt and dust particles contained in the exhaust air.  Check the drain line 
operation by filling the drain pan under the unit with water, clean the U-trap and the drain line, if necessary.

5. Supply air flow control (twice per year).

The supply duct grille may get clogged with leaves and other objects reducing the unit performance and supply air delivery. 
Check the supply grille twice per year and clean it as required.

6. Technical maintenance of air duct system (every 5 years).

Even regular fulfilling of all the prescribed above maintenance operations may not completely prevent dirt accumulation in the air ducts 
which reduces the unit capacity.  Duct maintenance means regular cleaning or replacement.

TECHNICAL MAINTENANCE

DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE 

OPERATIONS!

ENSURE THAT THE UNIT IS SWITCHED OFF FROM THE SUPPLY MAINS BEFORE 

REMOVING THE GUARD.

Содержание VUE 300 H2 MINI EC A14

Страница 1: ...C A2 VUT 300 H2 MINI EC A2 VUE 300 V2 MINI EC A2 VUE 300 H2 MINI EC A2 VUT 300 V2 MINI EC A14 VUT 300 H2 MINI EC A14 VUE 300 V2 MINI EC A14 VUE 300 H2 MINI EC A14 Heat and energy recovery air handling unit USER S MANUAL ...

Страница 2: ...TION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation operations The unit must be grounded Do not lay the power cable of the unit in close proximity to heating equipment While installing the unit follow the safety regulations specific to the use of electric tools This user s manual is a main operating document intended for technical maintenance and op...

Страница 3: ...it against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during operation Do not direct th...

Страница 4: ... PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN PURPOSE The unit is designed to ensure continuous mechanical air exchange in houses offices hotels cafes conference halls and other utility and public spaces as well as to recover the heat energy contained in the air extracted from the premises to warm up the f...

Страница 5: ...idity recovery efficiency according to EN 13141 7 VUT VUE 300 V2 mini EC VUT VUE 300 H2 mini EC 287 287 810 714 447 447 C 495 154 78 105 246 154 80 B A ø122 ø122 B A 171 135 42 143 714 C MODEL A B C VUT VUE 300 V2 mini EC A2 150 110 43 VUT VUE 300 H2 mini EC A2 150 110 43 VUT VUE 300 H2 mini EC A14 198 255 63 VUT VUE 300 H2 mini EC A14 164 295 63 TECHNICAL DATA The unit is designed for application...

Страница 6: ... with a temperature sensor for units with an A14 control panel or a thermostat for units with an A2 control panel The temperature sensor is installed in the exhaust air duct downstream of the heat exchanger In case of a freezing danger the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow The recommended sensor or thermostat operating temperature is 3 C exhaus...

Страница 7: ...e covered with a protecting grille or other protecting device with mesh width not more than 12 5 mm While installing the unit ensure convenient access for subsequent maintenance and repair The unit must be mounted on a plane wall Installing the unit to an uneven surface could lead to the unit s casing distortion and operation disturbance The unit is designed for mounting on a horizontal plane as w...

Страница 8: ...ting brackets SUSPENDED MOUNTING When selecting a mounting location of the unit check the minimum allowable distances to it Mounting using U shaped mounting brackets only for theVUE units Attach the mounting brackets to the ceiling The mounting bracket must be installed in consideration of the ceiling material and the unit weight 260 mm Install the unit on the mounting brackets Tighten the fixing ...

Страница 9: ...ber Nut and lock nut min 400 mm min 400 mm Mounting using L shaped mounting brackets with the service panel on the left min 250 mm min 400 mm UNIT FLOOR MOUNTING Install the unit on the pre mounted floor supports minimum 150 mm height to ensure sufficient access for the drain pipe connection to the U trap and for condensate drain system installation 150 mm 150 mm THE UNIT MUST BE MOUNTED ON A PLAN...

Страница 10: ...0 H2 mini EC A14 unit example Humidity sensor Mount Exhaust air duct Control unit socket Control unit connector SERVICE SIDE CHANGE Make sure of the correct unit service side selection Unit mounting position should enable free excess to the service panel for maintenance and service operations Extract air Extract air Intake air Intake air Exhaust air Exhaust air Supply air Supply air Extract air In...

Страница 11: ...Then unscrew six fixing screws from the back panel and remove the panel Install the back panel on the opposite side of the unit 3 Install the latches and the service panel on the opposite side of the unit Service side change is shown by the example of the VUT VUE 300 V2 mini EC air handling unit The procedure of the service side changing for the VUT VUE 300 H2 mini EC unit is carried out in the sa...

Страница 12: ...Remove the plug from the hole open the service panel and install the drain pipe from the delivery set into the hole then connect the drain pipe to the sewage system using the SG 32 U trap kit available upon separate order Drain hose min 3 Sewage system Sewage pipe Ø 32 mm U trap Drain pipe The VUE 300 V2 H2 mini EC energy recovery units do not require condensate drainage as they are equipped with ...

Страница 13: ... WITH THE UNIT THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER S LABEL ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY DO NOT LAYTHE POWER CABLE OFTHE UNIT IN CLOSE PROXIMITY AND PARALLELTOTHE CONTROL PANEL CABLE DO NOT COILTHE CONTROL PANEL CABLEWHILE LAYING ITS OUT...

Страница 14: ...upply air damper SM2 exhaust air damper The air dampers and the actuator are not included in the delivery set and can be purchased separately For controlling the air dampers use the LF 230 BELIMO electric actuator with a voltage of 230 V and an open close controlling Connect the electric actuators to the 12 and 13 terminals refer to the External wiring diagram External control units wiring diagram...

Страница 15: ...ular cleaning is required To clean the heat exchanger pull it out flush the heat exchanger with warm detergent solution After cleaning install the dry heat exchanger back to the unit To remove the filters and the heat exchanger follow the operations described in Fig 19 1 Release the latches and remove the bottom panel 2 Open the unit panel 3 Remove the heat exchanger 4 Technical maintenance of con...

Страница 16: ...16 VUT VUE 300 V2 H2 mini EC www ventilation system com TECHNICAL MAINTENANCE OF THE UNIT 1 2 3 4 ...

Страница 17: ... fan impeller is soiled Clean the impellers The fan or casing screw connection is loose Tighten the screw connection of the fans or the casing against stop Water leakage only for VUT V2 H2 300 mini EC The drainage system is soiled damaged or installed incorrectly Clean the drain line Check the drain line slope angle Make sure that the U trap is filled with water and the drain pipes are frost prote...

Страница 18: ...uitable hoist machinery for handling and storage operations to prevent possible damage to the unit Follow the handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage The unit must be transported only in the working position Avoid sharp blows sc...

Страница 19: ...ller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual User ...

Страница 20: ...20 VUT VUE 300 V2 H2 mini EC www ventilation system com ...

Страница 21: ...21 www ventilation system com ...

Страница 22: ...22 VUT VUE 300 V2 H2 mini EC www ventilation system com ...

Страница 23: ...FICATE The VUT VUE 300___ mini EC A _____ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standar...

Страница 24: ...V161EN 03 ...

Отзывы: