EXTERNAL CONNECTION DIAGRAM FOR A2 AUTOMATION SYSTEM

1

2

3

5

8

6

7

4

L

N

PE

+10V

CTR

GND

L

N

PE

+10V

CTR

GND

+10V

48V

C

TR

GND

QF

XP

Power supply 

230 V/50 (60) Hz

EXTERNAL CONNECTIONS DIAGRAM FOR A14 AUTOMATION SYSTEM

A14 SENSOR CONTROL PANEL MOUNTING

Technical requirements to a cable for connection of the control panel to the unit: type - 4x0.25 mm

2

, length - up to 10 m. The control 

panel should be connected to the terminals 8, 9, 10 ad 11 of the X2 terminal block (refer to the External wiring diagram).
The unit has an option of additional external controls connection to the X2 terminal block, which is located on the hinged electrical 
mounting plate of the control unit.  Extra connections to the unit are shown in dotted lines in the External wiring diagram.

Connection of the automatic fire fighting system contact (PK)

Upon connecting the automatic fire extinguishing system contact remove the jumper between the terminals 1 and 2.  In case of fire, the 
normally closed dry contact breaks the control circuit from the central fire-fighting board and cuts off power supply to the unit.

CONNECTION TO POWER MAINS

POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.

THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.

THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE 

MANUFACTURER’S LABEL.

ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED  

AND WILL VOID THE WARRANTY.

DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE 

PROXIMITY AND PARALLEL TO THE CONTROL PANEL CABLE! DO 

NOT COIL THE CONTROL PANEL CABLE WHILE LAYING ITS OUT.

•  The unit is rated for connection to 230 V / 50 (60) Hz power mains. 
•  The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section 

selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, 
length and installation method. 

•  The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric 

circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown 
of the unit. The trip current of the automatic circuit breaker 

QF

 must exceed the maximum current consumption of the unit (refer 

to the technical data table).  The recommended trip current of the circuit breaker is the next current in the standard trip current row 
following the maximum current of the connected unit.  The automatic circuit breaker is not included in the delivery set.

Содержание VUE 300 H2 MINI EC A14

Страница 1: ...C A2 VUT 300 H2 MINI EC A2 VUE 300 V2 MINI EC A2 VUE 300 H2 MINI EC A2 VUT 300 V2 MINI EC A14 VUT 300 H2 MINI EC A14 VUE 300 V2 MINI EC A14 VUE 300 H2 MINI EC A14 Heat and energy recovery air handling unit USER S MANUAL ...

Страница 2: ...TION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation operations The unit must be grounded Do not lay the power cable of the unit in close proximity to heating equipment While installing the unit follow the safety regulations specific to the use of electric tools This user s manual is a main operating document intended for technical maintenance and op...

Страница 3: ...it against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during operation Do not direct th...

Страница 4: ... PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN PURPOSE The unit is designed to ensure continuous mechanical air exchange in houses offices hotels cafes conference halls and other utility and public spaces as well as to recover the heat energy contained in the air extracted from the premises to warm up the f...

Страница 5: ...idity recovery efficiency according to EN 13141 7 VUT VUE 300 V2 mini EC VUT VUE 300 H2 mini EC 287 287 810 714 447 447 C 495 154 78 105 246 154 80 B A ø122 ø122 B A 171 135 42 143 714 C MODEL A B C VUT VUE 300 V2 mini EC A2 150 110 43 VUT VUE 300 H2 mini EC A2 150 110 43 VUT VUE 300 H2 mini EC A14 198 255 63 VUT VUE 300 H2 mini EC A14 164 295 63 TECHNICAL DATA The unit is designed for application...

Страница 6: ... with a temperature sensor for units with an A14 control panel or a thermostat for units with an A2 control panel The temperature sensor is installed in the exhaust air duct downstream of the heat exchanger In case of a freezing danger the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow The recommended sensor or thermostat operating temperature is 3 C exhaus...

Страница 7: ...e covered with a protecting grille or other protecting device with mesh width not more than 12 5 mm While installing the unit ensure convenient access for subsequent maintenance and repair The unit must be mounted on a plane wall Installing the unit to an uneven surface could lead to the unit s casing distortion and operation disturbance The unit is designed for mounting on a horizontal plane as w...

Страница 8: ...ting brackets SUSPENDED MOUNTING When selecting a mounting location of the unit check the minimum allowable distances to it Mounting using U shaped mounting brackets only for theVUE units Attach the mounting brackets to the ceiling The mounting bracket must be installed in consideration of the ceiling material and the unit weight 260 mm Install the unit on the mounting brackets Tighten the fixing ...

Страница 9: ...ber Nut and lock nut min 400 mm min 400 mm Mounting using L shaped mounting brackets with the service panel on the left min 250 mm min 400 mm UNIT FLOOR MOUNTING Install the unit on the pre mounted floor supports minimum 150 mm height to ensure sufficient access for the drain pipe connection to the U trap and for condensate drain system installation 150 mm 150 mm THE UNIT MUST BE MOUNTED ON A PLAN...

Страница 10: ...0 H2 mini EC A14 unit example Humidity sensor Mount Exhaust air duct Control unit socket Control unit connector SERVICE SIDE CHANGE Make sure of the correct unit service side selection Unit mounting position should enable free excess to the service panel for maintenance and service operations Extract air Extract air Intake air Intake air Exhaust air Exhaust air Supply air Supply air Extract air In...

Страница 11: ...Then unscrew six fixing screws from the back panel and remove the panel Install the back panel on the opposite side of the unit 3 Install the latches and the service panel on the opposite side of the unit Service side change is shown by the example of the VUT VUE 300 V2 mini EC air handling unit The procedure of the service side changing for the VUT VUE 300 H2 mini EC unit is carried out in the sa...

Страница 12: ...Remove the plug from the hole open the service panel and install the drain pipe from the delivery set into the hole then connect the drain pipe to the sewage system using the SG 32 U trap kit available upon separate order Drain hose min 3 Sewage system Sewage pipe Ø 32 mm U trap Drain pipe The VUE 300 V2 H2 mini EC energy recovery units do not require condensate drainage as they are equipped with ...

Страница 13: ... WITH THE UNIT THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER S LABEL ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY DO NOT LAYTHE POWER CABLE OFTHE UNIT IN CLOSE PROXIMITY AND PARALLELTOTHE CONTROL PANEL CABLE DO NOT COILTHE CONTROL PANEL CABLEWHILE LAYING ITS OUT...

Страница 14: ...upply air damper SM2 exhaust air damper The air dampers and the actuator are not included in the delivery set and can be purchased separately For controlling the air dampers use the LF 230 BELIMO electric actuator with a voltage of 230 V and an open close controlling Connect the electric actuators to the 12 and 13 terminals refer to the External wiring diagram External control units wiring diagram...

Страница 15: ...ular cleaning is required To clean the heat exchanger pull it out flush the heat exchanger with warm detergent solution After cleaning install the dry heat exchanger back to the unit To remove the filters and the heat exchanger follow the operations described in Fig 19 1 Release the latches and remove the bottom panel 2 Open the unit panel 3 Remove the heat exchanger 4 Technical maintenance of con...

Страница 16: ...16 VUT VUE 300 V2 H2 mini EC www ventilation system com TECHNICAL MAINTENANCE OF THE UNIT 1 2 3 4 ...

Страница 17: ... fan impeller is soiled Clean the impellers The fan or casing screw connection is loose Tighten the screw connection of the fans or the casing against stop Water leakage only for VUT V2 H2 300 mini EC The drainage system is soiled damaged or installed incorrectly Clean the drain line Check the drain line slope angle Make sure that the U trap is filled with water and the drain pipes are frost prote...

Страница 18: ...uitable hoist machinery for handling and storage operations to prevent possible damage to the unit Follow the handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage The unit must be transported only in the working position Avoid sharp blows sc...

Страница 19: ...ller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual User ...

Страница 20: ...20 VUT VUE 300 V2 H2 mini EC www ventilation system com ...

Страница 21: ...21 www ventilation system com ...

Страница 22: ...22 VUT VUE 300 V2 H2 mini EC www ventilation system com ...

Страница 23: ...FICATE The VUT VUE 300___ mini EC A _____ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standar...

Страница 24: ...V161EN 03 ...

Отзывы: