Ventilation supply unit
OPERATING MANUAL
V29-1_EN-03.indd 1
18.10.2016 10:38:45
Страница 1: ...Ventilation supply unit OPERATING MANUAL V29 1_EN 03 indd 1 18 10 2016 10 38 45...
Страница 2: ...e Mounting Connection to electric network External devices VPA control Control panel Switching on and switching off VPA Programming the modes using control panel Emergency situations Storage rules Man...
Страница 3: ...mically active fumes dust carbon black etc to residential and public buildings individual houses offices hotels conference halls and other premises and for providing the required quality of the air Th...
Страница 4: ...ngle of 15 Example of design letters Ventilation input unit VPA diameter of connecting tubes 150 mm heater power 6 0 kW phase connection VENTS VPA 150 6 0 3 Basic technical parameters correspond to va...
Страница 5: ...eight kg 52 62 VPA 100 1 8 1 VPA 125 2 4 1 VPA 150 2 4 1 VPA 150 3 4 1 VPA 150 5 1 3 VPA 150 6 0 3 VPA 200 3 4 1 VPA 200 5 1 3 VPA 200 6 0 3 Voltage V 50 Hz 1 230 1 230 3 400 1 230 3 400 Maximum fan p...
Страница 6: ...PA 100 99 382 421 5 408 800 647 VPA 125 124 382 421 5 408 800 647 VPA 150 149 455 496 5 438 800 647 VPA 200 199 487 526 5 513 835 684 VPA 250 249 487 526 5 513 835 684 VPA 315 314 527 566 5 548 900 75...
Страница 7: ...signation only It is prohibited to connect control panel and sensors to control panel and to carry out the works inside VPA if it is connected to power supply and the switch is in I position On Never...
Страница 8: ...oled 90 thermal switch with automatic restart of VPA using manual recovery Sensors of the emergency thermal switch shutoff circuits and don t return VPA to operating condition To recover VPA it is nec...
Страница 9: ...9 Fig 2 V29 1_EN 03 indd 9 18 10 2016 10 38 49...
Страница 10: ...wn it is necessary to take into consideration the VPA weight and material to which the unit is attached using all mounting L holders containing the antivibration inserts and attached to unit base fig...
Страница 11: ...phase electric network is shown in fig 5 Connecting VPA is carried out using the terminal block inside the control unit according to electric connection diagram and terminals designation fig 4 or fig...
Страница 12: ...res and external devices sensors shutter drive control panel etc Circuit breaker QF shall be located in a manner which ensures free access to it for the unit operative shutoff Number wires and their c...
Страница 13: ...6 0 3 400 V 16 5 2 5 VPA 250 3 6 3 400 V 10 5 2 5 VPA 250 6 0 3 400 V 16 5 2 5 VPA 250 9 0 3 400 V 25 5 2 5 VPA 315 6 0 3 400 V 16 5 2 5 VPA 315 9 0 3 400 V 25 5 2 5 VPA 1 315 6 0 3 400 V 16 5 2 5 VPA...
Страница 14: ...esired place the screw head should tightly press the cover to wall and under no circumstances contact with the panel electronic board since otherwise the risk of equipment damage appears remove protec...
Страница 15: ...e sensor is ensured fig 6 The channel sensor is connected to control unit with the help of supplied cable 4 m long The contacts X1 8 and X1 9 polarity is indifferent located in the terminal block are...
Страница 16: ...uits is executed using two terminal blocks installed on the con trol unit see fig 7 and 8 Fan heater heater control opto triac unit control unit chan nel temperature sensor and differential pressure s...
Страница 17: ...17 Fig 7 Control unit for single phase electric network 230 V 50 Hz Cover is not shown V29 1_EN 03 indd 17 18 10 2016 10 38 51...
Страница 18: ...2 Temperature sensor 10 Control panel 11 B Control panel 12 A Control panel 13 Control panel 14 Y N Shutter drive 15 Y LC Shutter drive 16 Y LO Shutter drive 17 PK1 Fire fighting system NC contact 18...
Страница 19: ...19 Fig 8 Control unit for single phase electric network 400 V 50 Hz Cover is not shown V29 1_EN 03 indd 19 18 10 2016 10 38 52...
Страница 20: ...K1 2 Temperature sensor 10 Control panel 11 B Control panel 12 A Control panel 13 Control panel 14 Y N Shutter drive 15 Y LC Shutter drive 16 Y LO Shutter drive 17 PK1 Fire fighting system NC contact...
Страница 21: ...2 X1 13 for control panel connection contacts X1 17 X1 18 for connecting the automatic ire extinguishing circuit signal contacts X1 19 X1 20 for hygrostat connection contacts X1 8 X1 9 for channel tem...
Страница 22: ...e of tubular electric heating elements operation to maintain the required temperature in the channel The control panel is equipped with temperature sensor that allows maintaining desired set by the us...
Страница 23: ...moves downwards or increasing the current parameter 6 Enter button selecting parameter for change or switching to lower level of menu in the main operating window menu activation 7 Escape button retur...
Страница 24: ...creen To switch off VPA it is necessary to press the Power button indicator will display the VPA current status selection menu select option Off and press Enter button The screen displays information...
Страница 25: ...main menu and service menu Entering into menu from the main operating window is carried out by pressing the Enter button Up Down buttons are used for switching between the items Return to previous lev...
Страница 26: ...the value of fan speed Up Down buttons Date and time setup is required for correct operation of the day timer and the week timer Service menu allows to user to enable and set the service functions Cl...
Страница 27: ...lected position is carried out using the Up Down buttons Filter replacement timer Allows to user to determine the time interval after which the control panel will be switched to reminding mode for tim...
Страница 28: ...current operating mode position of the main operating window Table containing the reminder periodically for short time period substitutes for the main operatingwindow theredLEDisflashing Todisablether...
Страница 29: ...k After activation of this mode VPA will automatically according to set parameters change the fan speed and temperature of governing at set time of set days of week At enabled week timer the symbol H...
Страница 30: ...tching to VPA On Off mode Up Down buttons and Power button allow selecting the desired position Enter button allows switching VPA to corresponding status On Off At switching off VPA the following algo...
Страница 31: ...clogging operation of the differential pressure or communication line fault the unit is switched to emergency shutoff mode tubular electric heating elements blowing with further shutoff in 2 minutes R...
Страница 32: ...shutoff cause removethecontrolunitcoverandcheckthesafetydevices replacethefaultydevicesbythe new ones with the same parameters if you failed to eliminate the failure don t switch on VPA and invite the...
Страница 33: ...n network under the condition of transportation storage mounting and operation rules observation In the event of absence of on sale date the warranty period is calculated from release date In case of...
Страница 34: ...intervention VPA owner must follow the guidelines Ventilation inlet unit VPA_______ complies with technical requirements and is judged as ready for operation Acceptor mark Release date Seller Name of...
Страница 35: ..._________________________________________________________________________ COMMISSIONING CERTIFICATE WARRANTY CARD _____________________________________________________________ ________________________...
Страница 36: ...V29 1EN 03 V29 1_EN 03 indd 36 18 10 2016 10 38 54...