USER’S MANUAL

VKP EC

InlIne centrIfugal fan

Содержание VKP 1000x500 L3 EC

Страница 1: ...USER S MANUAL VKP EC Inline centrifugal fan ...

Страница 2: ... at the time of the document s preparation The Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means in any information search system or translated into an...

Страница 3: ... operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation operations Unpack the unit with care The unit must be grounded While installing the unit follow the safety regulations specific to the use of electric tools Do not change the power cable length at your own discretion Do not bend the power cable Avoid damaging the power cable ...

Страница 4: ...ances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during operation Do not direct the air flow produced by the unit towards open flame or ignition sources Do not block the air duct when the unit is switched on In case of continuous operation of the unit periodically check the s...

Страница 5: ... CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN PURPOSE The centrifugal fan in a sound insulated casing is designed for supply and exhaust ventilation of domestic public and industrial premises with high requirements to the noise level and with limited space for mounting ...

Страница 6: ...up to 45 C and relative humidity up to 80 The unit is rated as a Class I electrical appliance Hazardous parts access and water ingress protection rating for the unit connected to the air ducts IPX4 The unit design is constantly being improved thus some models may be slightly different from those described in this manual VKP 600х350 М1 ЕС VKP 600х350 L3 ЕС VKP 700х400 M1 ЕС VKP 700x400 L3 ЕС VKP 80...

Страница 7: ...500 520 540 250 270 290 328 530 17 9 VKP 500x300 L1 EC 500 520 540 300 320 340 410 530 18 7 VKP 600x300 M1 EC 600 620 640 300 320 340 407 650 24 1 VKP 600x350 M1 EC 600 620 640 350 370 390 457 650 25 2 VKP 600x350 LЗ EC 600 620 640 350 370 390 512 650 36 0 VKP 700x400 M1 EC 700 720 740 400 420 440 496 750 42 2 VKP 700x400 LЗ EC 700 720 740 400 420 440 555 750 43 0 VKP 800x500 MЗ EC 800 820 840 500...

Страница 8: ...d make sure the impeller has smooth rotation prior to mounting The fans are mounted into the rectangular ducts and require no special fixing in case of direct connection Connect the fan to air ducts with M8 bolts and nuts The fans can be mounted in any position with respect to the airflow direction which is indicated with a pointer on the casing Access for the fan maintenance shall be provided The...

Страница 9: ...r built into the stationary wiring to open the electric circuit in case of overload or short circuit The circuit breaker installation place must provide quick access for emergency shutdown of the unit The trip current of the automatic circuit breaker QF must exceed the maximum current consumption of the unit refer to the technical data table The recommended trip current of the circuit breaker is t...

Страница 10: ...eller blades require thorough cleaning once in 6 months Detach air ducts from the fan before starting maintenance works Clean the impeller blades with a soft cloth wetted in mild water detergent solution Avoid liquid dripping on the motor Wipe the fan surfaces dry after cleaning While cleaning the fan make sure the balance counterweights are not shifted and the impeller is not misaligned 1 3 4 5 6...

Страница 11: ...equirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage The unit must be transported only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transportation at low tempera...

Страница 12: ...e Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual U...

Страница 13: ... certify acceptance of the complete unit delivery with the user s manual The warranty terms are acknowledged and accepted Customer s Signature INSTALLATION CERTIFICATE The VKP _____________ EC unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The uni...