USER’S MANUAL

Содержание ICF Series

Страница 1: ...ICF Impulse centrifugal fan USER S MANUAL...

Страница 2: ...of the document s preparation The Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technologica...

Страница 3: ...life of the unit While transferring the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power...

Страница 4: ...ldren to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit...

Страница 5: ...or explosive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substan...

Страница 6: ...n this manual Model Dimensions mm Weight kg A B C E F H L K ICF 50N 290 1355 935 1005 1065 90 180 350 96 ICF 85N 330 1605 1105 1175 1235 110 230 390 136 ICF 100N 330 1605 1105 1175 1235 110 230 390 13...

Страница 7: ...single speed ICF 85N 4 3 400 50 9750 2 2 85 22 3 1500 25 55 C 55 C ICF 85N 4 200 2 200 C 2 hours F200 ICF 85N 4 300 2 300 C 2 hours F300 ICF 85N 4 400 2 400 C 2 hours F400 85N double speed ICF 85N 4...

Страница 8: ...equipped with a single speed 4 pole motor or a double speed 4 6 or 4 8 pole asynchronous motor Steel impeller with backward curved blades Before installing the unit carry out the following checks Mak...

Страница 9: ...its insulation length and installation method i e overhead in pipes or inside the walls Connection of the fan for smoke extraction must be performed via a cable with a respective fire resistance clas...

Страница 10: ...peed Wiring diagram for the fan operation with high speed Single speed ICF 50N 4 ICF 85N 4 ICF 100N 4 X1 L3 L1 L2 U1 W1 V1 U2 W2 V2 PE L2 L3 L1 1 2 3 4 5 6 400 V 50 Hz 400 V 60 Hz Double speed ICF 50N...

Страница 11: ...of the driven mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the fo...

Страница 12: ...Standard switching equipment automatic circuit breakers contactors and motor starters is not designed to withstand prolonged overloads normally causing the fan to shut down automatically DOL starting...

Страница 13: ...lt connecting the motor shaft to the hub for proper tightness and tighten it up if necessary Check the bolt connecting the motor shaft to the hub for proper tightness and tighten it up if necessary Te...

Страница 14: ...regulations and equipment specifications The installed automatic circuit breaker is of poor quality or its actual performance falls short of the rated values stated by the manufacturer Re select the...

Страница 15: ...Impeller contamination with foreign objects or debris Clean the impeller from foreign objects or debris Increased noise vibration in the fan Loose screw connections Check the screw connections for pr...

Страница 16: ...ssible damage to the unit Follow the handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protec...

Страница 17: ...pair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminated by means of replac...

Страница 18: ...18 ICF www ventilation system com...

Страница 19: ...IFICATE The ICF _______________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician...

Страница 20: ...V117EN 03...