background image

3

www.ventilation-system.com

SAFETY REQUIREMENTS

All user’s manual requirements as well as the provisions of all the applicable local and national 
construction, electrical, and technical norms and standards must be observed when installing 
and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and 
repair operations. 

Only  qualified electricians with a work permit for electrical units up to 1000 V are 

allowed for installation and maintenance. The present user’s manual should be carefully 

read before beginning works.

•  Check the unit for any visible damage of the impeller, the casing, and the grille before starting 

installation. The casing internals must be free of any foreign objects that can damage the 
impeller blades. 

•  While mounting the unit, avoid compression of the casing! Deformation of the casing may 

result in motor jam and excessive noise.

•  Misuse of the unit and any unauthorised modifications are not allowed.
•  Do not expose the device to adverse atmospheric agents (rain, sun, etc.).
•  Transported air must not contain any dust or other solid impurities, sticky substances, or 

fibrous materials.

•  Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, 

insecticides, etc.

•  Do not close or block the intake or extract vents in order to ensure the efficient air flow.
•  Do not sit on the unit and do not put objects on it.
•  The information in this user’s manual was correct at the time of the document’s preparation. 
•  The Company reserves the right to modify the technical characteristics, design, or 

configuration of its products at any time in order to incorporate the latest technological 
developments.

WARNING! Similar to the use of any other household electrical appliances when 

operating this fan, the following basic rules must be followed:

•  Never touch the unit with wet or damp hands.
•  Never touch the unit when barefoot.
This appliance is not intended for use by persons (including children) with reduced physical, 
sensory or mental capabilities, or lack of experience and knowledge, unless they have been 
given supervision or instruction concerning use of the appliance by a person responsible for 
their safety.
Children should be supervised to ensure that they do not play with the appliance.
The connection to the supply mains must be made through a means of disconnection, 
which is incorporated in the fixed wiring in accordance with the wiring rules, and has a 
contact separation in all poles that allows for full disconnection under overvoltage category III 
conditions.

Содержание Boost 355

Страница 1: ...Boost 355 Boost 400 Inline mixed flow fan USER S MANUAL...

Страница 2: ...ertificate 13 Warranty card 13 This user s manual is a main operating document intended for technical maintenance and operating staff The manual contains information about purpose technical details op...

Страница 3: ...a hazardous or explosive environment containing spirits gasoline insecticides etc Do not close or block the intake or extract vents in order to ensure the efficient air flow Do not sit on the unit and...

Страница 4: ...rnal switching device such as a timer or connected to a circuit that is regularly switched on and off by the utility Precautions must be taken to avoid the back flow of gases into the room from the op...

Страница 5: ...res evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogeni...

Страница 6: ...Voltage V at 50 Hz 1 230 Power W 126 131 150 197 204 224 Current A 0 60 0 58 0 66 0 91 0 90 0 98 Maximum air flow m3 h 2090 2296 2485 2677 3136 3350 RPM min 1 1350 1400 1470 1320 1390 1446 Maximum tr...

Страница 7: ...izontal or vertical surface While installing the unit ensure convenient access for subsequent maintenance and repair Fasteners for fan mounting are not included in the delivery set and should be order...

Страница 8: ...cted the internal parts of the unit must be protected from ingress of foreign objects To prevent uncontrollable access to the fans the spigots may be covered with a protecting grille or other protecti...

Страница 9: ...ors cables wires The actual wire cross section selection must be based on the maximum load current maximum conductor temperature depending on the wire type insulation length and installation method Th...

Страница 10: ...ons Disconnect the air ducts from the fan Clean the fans with a soft brush cloth vacuum cleaner or compressed air Do not use water aggressive solvents or sharp objects as they may damage the impeller...

Страница 11: ...up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours TROUBLESHOOTING Problem Possible reasons Troubleshooting The fan s do es not start...

Страница 12: ...Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual includin...

Страница 13: ...N CERTIFICATE The Boost_________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full...

Страница 14: ...14 Boost www ventilation system com...

Страница 15: ...15 www ventilation system com...

Страница 16: ...V208EN 04...

Отзывы: