20
6
MODBUS
6.1
CU24V
CONTROLLER
-
LIST
OF
REGISTERS
WITH
ADDRESS
(F
UNCTION
03,
06)
•
Protocol:
MODBUS RTU (See information on the RMC20 display)
•
Baud rate:
9600
•
Bit number:
8
•
Parity:
No
•
Stop bit:
1
•
Slave address:
1
6.1.1
S
ETTING THE SLAVE ADDRESS OF THE CONTROLLER
6.1.2
L
IST OF ADRESS
Warning
:
MODBUS address is the address that is specified directly in the MODBUS protocol frame,
Registers in the controller have double Modbus address. The second address is for use in the range
from 0 to 9999 because not all software are able to use address above 9999. To have access to the
second address just subtract the value 55536 from the address listed in the tables.
Items in red colour are not available.
Register Name
Register
MODBUS
Address
PWM outputs P
NOTE:
1. Control values are in w % with 1/10
precision. After reading the register value the
dot should be placed artificially Ex.: Reading
the value 257 should be treated as 25.7%
2. The value 0x8000 means, the parameter is
not available.
0
– P1
1 - P2
…
n - Pn
65472
65473
...
65472+n
0-10V analog outputs
NOTE:
1. Control values are in w % with 1/10
precision. After reading the register value the
0
– Y1
1
– Y2
…
n
– Yn
65408
65409
S1
S2
Address
1
2
3
4
1
2
3
4
□
□
□
□
□
□
□
□
1
■
□
□
□
□
□
□
□
2
□
■
□
□
□
□
□
□
3
■
■
□
□
□
□
□
□
4
■
■
■
■
■
■
■
□
255