Wiring Requirements

CORRECT LOCATION     When used as a duct sensor, this sensor should be mounted in the return air duct.  When used as 
a remote temperature sensor, the Duct Sensor should be mounted in an indoor location approximately five feet from the 
floor, close to or in a frequently used room, preferably on an inside partitioning wall or on a section of wall without pipes or 
ductwork.  Mount the sensor where temperature operating limits are within 32 to 99 F and the humidity operating range is 
within 0 to 95% relative humidity, non-condensing. 

INCORRECT LOCATIONS     The Duct Sensor should 

NOT

 be mounted close to a window, on an outside wall, or next to a 

door leading to the outside.  Do not mount the sensor in a location where it would be exposed to direct light and heat from 
a lamp, the sun, a fireplace, or any other temperature-radiating object which may cause a false reading.   Finally, do not 
mount  the  sensor  close  to  or  in  direct  airflow  from  supply  registers  or  return  air  grilles  and  in  areas  with  poor  air 
circulation (such as behind a door or in an alcove).

Sensor Location

CAT 5 Cable

Thermostat Cable

The Duct Sensor should be connected to the thermostat using solid conductor CAT 5, CAT 5e, or CAT 6 type network 
communication cable. This is an unshielded cable with four twisted pairs of 24 gauge solid wire; 

DO NOT use stranded 

cable

.  The cable length should not exceed 250 feet.  If less than 75 feet of cable is required to connect the thermostat to 

the Duct Sensor, a three conductor thermostat cable (18-24 gauge) may be used; this cable is NOT suitable for any length 
greater than 75 feet.

IMPORTANT:   Do no use shielded wire.   Do not run sensor wiring in the same conduit as the 24VAC thermostat wiring.   
Electrical interference may cause the sensor to give incorrect temperature readings.

NOTE:  All sensor wiring must be in compliance with all applicable local and national codes.

SAFETY CONSIDERATIONS

Read  and  follow  the  manufacturer  instructions  carefully.    All  wiring  must  conform  to  local  and  national 
electrical codes.  Improper wiring or installation may damage the sensor.

Recognize safety information.  This is the safety alert symbol       .  When the safety alert symbol is present on 
equipment or in the instruction manual, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAUTION.  These words are used with the safety alert 
symbol.   DANGER identifies the most serious hazards which will result in severe personal injury or death.   
WARNING signifies a hazard which could result in personal injury or death.   CAUTION is used to identify 
unsafe practices which may result in minor personal injury or property damage.  

The Duct Sensor measures indoor air temperature in the return air duct with a range of -40   to 127 F.   If used 
indoors as a remote temperature sensor, the sensor will read room temperature and send the information to 
the thermostat.   If used as a duct temperature sensor, this sensor may be used to provide duct temperature 
information (which is not used to control heating or cooling).

GENERAL

DIGITAL DUCT 

TEMPERATURE SENSOR

IMPORTANT:  READ ALL OF THESE INSTRUCTIONS BEFORE INSTALLING THE SENSOR.

©Venstar Inc. 08/07          

P/N 88-617     Rev. 1