ENERGY RECOVERY VENTILATOR
Venmar AVS S10 ERV
Part no. 41700
Low speed: 50 CFM (0.2 in. w.g.), selectable 65 CFM
High speed: 100 CFM (0.4 in. w.g.), selectable 85 CFM
VB0198
CONSTRUCTION
• 22 ga. galvanized steel housing and door
• One-piece molded insulation shell,
(expanded polystyrene; UL 94 HF-1 certifi ed)
• Galvanized steel 5" diameter ports*
• Steel door hinges and latches
• Cold side ports with plastic ring; allow vapor barrier sealing
• No drain required
*All units ports were created to be connected to ducts having a
minimum of 5” diameter, but if need be, they can be connected to
bigger sized ducts by using an appropriate transition (e.g.: 5” diameter
to 6” diameter transition).
MOTORS
• Two high reliability, external rotor PSC motors, totally enclosed and
thermally
protected
• Backward blowers, can support high static pressure environment
FILTERS
• Two washable 20 ppi reticulated polyester urethane foam fi lters,
UL 900 class 2 certifi ed
• Optional MERV 7 fi lter kit, part no.: 21030 (additional 0.1 in. w.g.
static pressure to be considered) (sold separately)
ERV CORE
• Crossfl ow aluminum-polymerized paper core, UL723 certifi ed
• Hydroscopic polymer exchange water by direct vapor transfer using
molecular transport without the need of condensation
• Constructed of alternate layers of corrugated aluminum material
and polymeric bactericide dessiccant impregnated media; will not
promote growth of mold or bacteria
• Unique rectangular fl ute design to provide very low pressure drop
values
Controls
• Integrated push-button control for Low or High speed operation.
• For a complete list of optional main and auxiliary controls available,
refer to the
Wall Control Compatibility Chart
on last pages of wall
controls
specifi cation sheet, available at www.venmar.ca.
• For more details about controls, refer to the
Main and auxiliary wal
l
controls
user guide, also available at www.venmar.ca.
• Removable terminal block included for quicker low voltage control
connections.
• LED indicator shows operating modes and error codes.
• Unit must be permanently energized, no control should be installed
on power supply of unit.
Air Flow
• Pressure taps and balancing chart to allow easier balancing of the
unit
• Integrated balancing/backdraft dampers in cold supply and cold
exhaust
ports
Defrost Cycles
• Choice of regular or extended defrost cycles, according to climatic
conditions
• To set extended defrost cycles, refer to unit installation manual
Requirements and standards
•
HVI certifi ed
• Complies with the UL 1812 requirements regulating the installation
of Energy Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Complies with CSA C444 requirements regulating the installation of
Energy
Recovery
Ventilators
R
EGULAR
D
EFROST
C
YCLES
O
UTSIDE
T
EMPERATURE
*
D
EFROST
IN
M
INUTES
/ A
IR
E
XCHANGE
IN
M
INUTES
°C
°F
L
OW
S
PEED
H
IGH
S
PEED
W
ARMER
THAN
-10
W
ARMER
THAN
14
N
O
DEFROST
N
O
DEFROST
FROM
-10
TO
-15
FROM
14
TO
5
6/40
9/40
FROM
-15
TO
-27
FROM
5
TO
-17
6/20
9/20
-27
AND
LESS
-17
AND
LESS
8/12
11/12
Warranty
The Venmar AVS S10 ERV is protected by a 5-year warranty on parts
only, with the original proof of purchase.
* Outside temperature is read by a thermistor located inside the unit,
next to fresh air from outside port.