background image

Round Fire and Combination Fire Smoke Dampers

6

Actuator and Temperature Response Device Connections

Actuator Connections

Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping 
diagrams developed in compliance with applicable codes, ordinances and regulations (see 

Electrical Guidelines

).

Duct to Sleeve Connections

Sleeve Gauge and Connection Type Requirements

Round duct connections shall be attached with #8 or #10 sheet metal screws as follows:
  • Ducts 22 in. (558mm) dia. and smaller shall have three screws.
  • Ducts larger than 22 in. (558mm) dia. up to and including 24 in. (610mm) dia. shall have five screws.

Note:

  All connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by Precision, 

DP1010 water base duct sealant manufactured by Design Polymerics, Grey Pookie, Ductmate PROseal®, or 
CL Ward S Seal applied in accordance with SMACNA recommendations.

Damper assemblies must be installed in wall and floor openings using a single retaining plate on either side of the 

wall/floor or by using a retaining plate on both sides of the wall/floor. A single retaining plate is provided with 
the dampers. A second retaining plate can be ordered as an option.

 •  The retaining plate(s) will open up for easy installation when the clamping screw is loosened. If necessary, remove 

the clamping screw and nut (see 

Figure 7

).

 •  Position the retaining plate between the blade axle and the 

actuator shaft as shown in 

Figure 5 & 6

. Do not place 

the retaining plate in the groove. IMPORTANT: The 
clamping mechanism should face away from the wall/
floor.

 •  Place the damper and attached retaining plate into the 

wall/floor opening.

 •  If a second retaining plate is being used, secure it on the 

opposite side of the wall/floor.

 •  Verify position, blade orientation, and actuator clearance 

then tighten the retaining plate clamping screws.

 •  The retaining plate(s) must overlap the wall/floor opening a 

minimum of 1 in. (25mm).

 •  Secure the retaining plate(s) to the wall at the four corners 

of each plate when two retaining plates are used 
and also within 3/4 in. (19mm) of the center of each 
side when one retaining plate is used. The following 
fasteners shall be used:

    -  #8 or #10 screws of a length such that the screw 

engages the steel stud/track by 1/2 in. (13mm)(steel 
framing).

    -  #8 or #10 screws of a length such that screw engages 

the wood stud by 13/4 in. (44mm) (wood framing)

    -  Steel anchors or self tapping concrete screws penetrating masonry or block by 11/4 in. (32mm).

Securing the Damper/Sleeve Assembly to Wall and Floor Openings

O 2 in.  Min.

1.00 in. Min. Typ.

Fasteners

Clamping

Screw

Nut

Retaining

Plate Assembly

Clamping Screw

Minimum Wall/Floor Opening

 = Nominal Dia. + 7/8 in. 

Figure 7: Retaining Plates

Содержание DFDR Series

Страница 1: ...eiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Ch...

Страница 2: ...terials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to prevent overspray if wall text...

Страница 3: ...rs must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Figure 1 12 in 24 in o c Maximum Floor Runner 2 in Ceiling Runner 2 Panhead Screws 24 i...

Страница 4: ...assembly to allow for this expansion The wall floor opening must be a minimum of 7 8 in 22mm larger than the outside diameter of the damper Clearances Required Between Damper Sleeves and Wall Floor O...

Страница 5: ...ITION INDICATOR AND OR ELECTRIC LINK DUCT CONNECTION AREA 2 00 IN 1 50 IN Optional Second Retaining Plate Do not place retainer plate in this groove Figure 5 FSDR SEFSDR SSFSDR Inserting Damper into W...

Страница 6: ...p for easy installation when the clamping screw is loosened If necessary remove the clamping screw and nut see Figure 7 Position the retaining plate between the blade axle and the actuator shaft as sh...

Страница 7: ...ensor with the lower temperature setting can be bypassed by an external contact closure allowing the damper to reopen until the secondary temperature is reached the sensor with the higher temperature...

Страница 8: ...he latest editions of NFPA 80 90A 92 101 105 UL864 AMCA 503 03 and local codes Actuator manufacturer recommendations Damper Troubleshooting The following is a possible cause and correction list for co...

Отзывы: