User Manual
SINGLE-PHASE ACTIVE ENERGY METER
Read all the instructions carefully
V3IS00417-010-082010
Mod.
Energy-230 LC
The
Energy-230 LC
static energy meter is an appliance to read active energy in single-phase
230V systems. It is designed to operate in environments with measurement category III and
pollution level 2 according to EN 61010-1 standard.
SAFETY WARNINGS
To guarantee correct installation, proceed as follows:
1) The appliance should be installed by a qualified operator
2) The appliance should be installed in a panel in such a way as to guarantee that the
terminals are inaccessible after fitting
3) A protection device against over-currents should be installed in the electrical system,
upstream of the energy meter
4) Connect the instrument as shown in the alongside diagrams
5) Before touching the connector terminals make sure that the wires to be connected or
already connected to the instrument are not live
6) Do not power or connect the instrument if any part of it is damaged
8) The instrument must be installed and activated in compliance with current electric
systems standards.
Code Model
Description
VN960100 Energy-230
LC
Single-phase active energy meter
TECHNICAL SPECIFICATIONS
• Power supply: 230 V CA (-15%/+10%), 50/60 Hz
• Maximum power consumption: 4 VA
• Basic current: I
b
= 15A
• Maximum current: I
MAX
= 22,5 A
• Starting
current:
)
50 mA
• Current circuit consumption: < 2 VA
• Operating temperature: -10 ÷ +45 °C
• Storage temperature: -20 ÷ +60 °C
• Relative humidity: 10% ÷ 90% non-condensing
• Connection type: direct for current conductors
• Signaling leds: green = power on
red = flashing at 10Wh
• Accuracy: class 2 (EN 62053-21)
• Display: 6-digit mechanical counter
• Reading resolution: 0,1 kWh (full scale: 99999,9 kWh)
• Housing: 2 DIN, gray RAL 7035
• Protection degree: IP20/IP51 on the front
OPERATION
• In normal operation, the
green
led is on and
the
red led flashes in proportion to the
active power (flashing at 10Wh).
The meter counts the consumption of active power with a resolution of 0,1 kWh.
PHASE ERROR
• When the energy meter is turned on, a connection check-up is automatically carried out
to detect any connection errors: in case of improper connection, the
red
and
green
leds
flash alternate and the meter is locked.
Warning: to restore correct meter operation after an error reading has been
showed, switch the meter off, invert connections of voltage or current
and turn on again.
REFERENCE STANDARS
Conformity to EU directives:
2006/95/EC (Low Voltage)
2004/108/EC (EMC)
is declared with reference to the following harmonised standards:
EN 61010-1
and
EN 62053-21
Dimensions
Connection
Description