DESCRIPTION OF CONNECTION TERMINALS & INDICATORS
1 - 2 : 12-24V AC/DC
--
POWER INPUT
Connect to 12-24V AC or DC power supply. The (–) supply, Terminal (2) and (–) GND Terminal (12)
are the common grounding points of the keypad system. No selec�on jumper is required for the
full input voltage range. Connect DC power with the (+) and (–) polarity indicated; and there is no
polarity discrimina�on for AC power input.
3 - 4 - 5 : OUTPUT 1 --
DOOR LOCK
Output 1 is a relay controlled by the group 1 user codes. It consists of Normally Open (N.O.) and
Normally Closed (N.C.) dry contacts of 5 Amp maximum ra�ng for electric door lock actua�on.
Use
N.O. contact for Fail-secure
electric lock while
N.C. contact for Fail-safe.
The output contact is programmable for Start / Stop (toggle) mode or �mer mode from 1 to 999
seconds. See programming Loca�on 40-43 for the details.
6 - 7 - 8 : OUTPUT 2
a) Standard Version
This is an auxiliary relay output with 1 Amp ra�ng Normally Open (N.0.) and Normally Closed
(N.C.) dry contacts controlled by the group 2 user codes, which is ideal for controlling security
systems & automa�c operators. It is programmable for Start / Stop (toggle) opera�on or �ming
opera�on from 1 to 999 seconds.
See programming Loca�on 50- 53 for the details.
b) Bell Bu�on Version
Output 2 is controlled by the “BELL” bu�on on the keypad. It operates as long as the bell
bu�on is pressed. Use N.O. contact to trigger an op�onal door chime.
●
●
●
CONNECTION TERMINALS
DK-9350 / DK9380
BACK-LIT JUMPER
STANDARD
VERSION
BELL BUTTON
VERSION