AC310 Universal AC Drive Service Manual
3.3.2 Y Output Detection and Maintenance
1. After power on, use multimeter DC voltage to measure the voltage of Y port to COM, the
voltage is below 1V is qualified; after running, the voltage of Y port to COM is below
24±0.75V is qualified.
2. If the detected voltage value is abnormal, the Y terminal function is abnormal, check O6
and T2, replace the damaged components.
Resistances R208=820Ω/0402 R32=2K/0402
R33=20K/0402 R34=10K/0402
Capacitors
C92=10NF
Optocoupler
O6=EL3HL
triode (vacuum tube or transistor)
T2=MMBT4401LT1
Diodes
D1=1N4148WS
3.3.3 Relay Detection and Maintenance
1. TA-TC is normally open, TB-TC is normally closed, in case of failure, TA-TC is normally closed,
TB-TC is normally open.
2. TA-TB-TC output is abnormal, relay REL does not work, test O7, T1, REL2 is damaged.
Resistances
R6/R7/R16/R17/R26/R27/R11/R12/R1/R2=2.2
k/0805 R8/R18/R28/R13/R3=2K/0402
R9/R19/R29/R14/R4=12K/0402
Optocoupler
O9
、
O1
、
O3
、
O2
、
O4=EL3H4
Capacitors
C3/C7/C11/C5/C1=100nf/
0402
C4/C8/C31/C6/C2=1nf/04