6 Adjustment with the display and adjustment module
WEIGHTRAC 31 • 4 … 20 mA/HART - four-wire
42374-EN-131119
To increase the Delta I value, you have to increase the distance of the
min. and max. adjustment points in the linearization.
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. through down-
stream indicating instruments or the input card of the control system.
You can simulate different values:
Pulse rate of the sensor
Process value
Current output
Switching function of the relay
Information:
The simulation is terminated automatically 60 minutes after the last
key has been pressed.
Info
In this menu you will find the following menu items:
•
Instrument name - shows instrument name and serial number
•
Instrument version - shows hardware and software version of the
instrument
•
Date of manufacture - shows calibration date and the date of the
last change
•
Instrument features - shows further instrument features
Diagnosis/Simulation