background image

20

10 Supplement

VEGATRENN 141 • 

52239-EN-210129

Max. connectable load 

1)

 

Ʋ

at 20 mA

600 Ohm

 

Ʋ

at 22 mA

550 Ohm

Deviation

Reference conditions

Calibration temperature 25 °C (77 °F)

Linearity

< 0.1 %

Influence of the ambient temperature

 

Ʋ

In the range of +20 … +60 °C 

(+68 … +140 °F)

< 0.2 %

 

Ʋ

In the range of -20 … +20 °C 

(-4 … +68 °F)

< 0.6 %

Deviation due to strong, high-frequency 

electromagnetic fields (EN 61326)

< 0.5 %

Integrated HART resistor

Resistance value

232 Ω

Indicators

LED displays

 

Ʋ

Status, operating voltage

LED green

 

Ʋ

Status, fault signal

LED red

Ambient conditions

Ambient temperature at the installation 

site of the instrument

-20 … +60 °C (-4 … +140 °F)

Storage and transport temperature

-40 … +70 °C (-40 … +158 °F)

Relative humidity

< 96 %

Mechanical environmental conditions

Vibrations (oscillations)

Class 4M4 acc. to IEC 60721-3-4 (1 g, 4 … 200 Hz)

Impacts (mechanical shock)

Class 6M4 acc. to IEC 60721-3-6 (10 g/11 ms, 

30 g/6 ms, 50 g/2.3 ms)

Electrical protective measures

Protection rating

IP20

Overvoltage category (IEC 61010-1)

 

Ʋ

up to 2000 m (6562 ft) above sea level II

 

Ʋ

up to 5000 m (16404 ft) above sea 

level

II - Only with connected overvoltage protection with 

response voltage of < 1000 V

 

Ʋ

up to 5000 m (16404 ft) above sea 

level

I

Protection class

II

1)

  Without internal HART resistor (when connecting to terminal 11/12).

Содержание VEGATRENN 141

Страница 1: ...Operating Instructions Ex separator for 4 20 mA sensors VEGATRENN 141 Document ID 52239...

Страница 2: ...ansport and storage 8 4 Mounting 9 4 1 General instructions 9 5 Connecting to power supply 10 5 1 Preparing the connection 10 5 2 Connection procedure 11 5 3 Wiring plan 12 6 Setup 13 6 1 Adjustment s...

Страница 3: ...3 Contents VEGATRENN 141 52239 EN 210129 Editing status 2021 01 27...

Страница 4: ...ntering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for successful work Note This symbol in...

Страница 5: ...afety instructions This is a state of the art instrument complying with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition...

Страница 6: ...nstallations in Canada shall comply with the relevant requirements of the Canadian Electrical Code 2 6 Safety instructions for Ex areas For Ex applications only devices with corresponding Ex approval...

Страница 7: ...he type label of the device or Enter serial number manually in the VEGA Tools app available free of charge in the respective stores 3 2 Principle of operation VEGATRENN 141 is an Ex ia separator with...

Страница 8: ...sport must be carried out in due consideration of the notes on the transport packaging Nonobservance of these instructions can cause damage to the device The delivery must be checked for completeness...

Страница 9: ...Around the ventilation slots there must be a distance of at least 2 cm to the next component VEGATRENN 141 is a corresponding intrinsically safe equipment and must not be installed in hazardous areas...

Страница 10: ...alues of EN 61326 for industrial areas shielded cable should be used In general cable screening is necessary in HART multidrop mode Connect the cable shielding on both ends to ground potential In the...

Страница 11: ...possible the current is limited to 4 mA An own unambiguous address address range 1 15 must be as signed to each connected sensor In this mode up to five sensors can be connected to one channel Inform...

Страница 12: ...sockets for connection of a HART handheld e g a VEGACONNECT 3 Processing circuit 4 20 mA HART active output 4 Processing circuit 4 20 mA HART active output with looped HART resis tor 5 Voltage supply...

Страница 13: ...mps LEDs 3 Hinged front cover 6 2 Adjustment elements Control lamps LED in the front plate indicate operation and fault signal Green operating control lamp lights in case of Mains voltage instrument i...

Страница 14: ...o adjustment or configuration of VEGATRENN 141 is necessary Via the HART communication sockets parameter adjustment of the connected HART sensors can be carried out without interrupting the measuring...

Страница 15: ...the fault and the measures taken the steps described in chapter Setup must be carried out again or must be checked for plausibility and completeness Should these measures not be successful please call...

Страница 16: ...1 52239 EN 210129 Attach the completed form and if need be also a safety data sheet outside on the packaging Please contact the agency serving you to get the address for the return shipment You can fi...

Страница 17: ...ote of chapters Mounting and Connecting to voltage sup ply and carry out the listed steps in reverse order 8 2 Disposal The device is made of recyclable materials For this reason it should be disposed...

Страница 18: ...found on our homepage 9 3 SIL conformity Instruments with SIL option fulfill the requirements of functional safety according to IEC 61508 You can find further information in the sup plied Safety Manua...

Страница 19: ...ss section 0 25 mm AWG 23 2 5 mm AWG 12 HART communication sockets 2 mm Voltage supply Operating voltage Nominal voltage AC 24 230 V 15 10 50 60 Hz Nominal voltage DC 24 65 V 15 10 Max power consumpti...

Страница 20: ...ns Ambient temperature at the installation site of the instrument 20 60 C 4 140 F Storage and transport temperature 40 70 C 40 158 F Relative humidity 96 Mechanical environmental conditions Vibrations...

Страница 21: ...Instruments with approvals can have different technical specifications depending on the version For that reason the associated approval documents of these instruments have to be carefully noted They a...

Страница 22: ...r www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de produ...

Страница 23: ...Control lamps 13 D Documentation 7 DTM 7 14 G Grounding 10 H HART 7 HART communication 7 10 14 HART multidrop 11 HART resistance 10 14 I Instrument return form 15 L LEDs 13 Load 10 P PACTware 7 14 Pot...

Страница 24: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: