34
10 Diagnostics and servicing
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-200806
Function check:
The instrument is being worked on, the measured
value is temporarily invalid (for example during simulation).
This status message is inactive by default.
Out of specification:
The measured value is unreliable because an
instrument specification was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required:
Due to external influences, the instrument
function is limited. The measurement is affected, but the measured
value is still valid. Plan in maintenance for the instrument because a
failure is expected in the near future (e.g. due to buildup).
This status message is inactive by default.
Code
Text message
Cause
Rectification
F013
no measured value
available
No measured value in the switch-on
phase or during operation
Check or correct installation and/or pa-
rameter settings
Clean the antenna system
F017
Adjustment span too
small
Adjustment not within specification
Change adjustment according to the limit
values (difference between min. and max.
≥ 10 mm)
F025
Error in the lineariza-
tion table
Index markers are not continuously rising,
for example illogical value pairs
Check linearization table
Delete table/Create new
F036
No operable software
Checksum error if software update failed
or aborted
Repeat software update
Send instrument for repair
F040
Error in the electronics
Limit value exceeded in signal processing
Hardware error
Restart instrument
Send instrument for repair
F080
General software error
General software error
Restart instrument
F105
Determine measured
value
The instrument is still in the start phase,
the measured value could not yet be de-
termined
Wait for the end of the switch-on phase
Duration up to 3 minutes depending on
the measurement environment and pa-
rameter settings
F260
Error in the calibration
Checksum error in the calibration values
Error in the EEPROM
Send instrument for repair
F261
Error in the instrument
settings
Error during setup
False signal suppression faulty
Error when carrying out a reset
Repeat setup
Carry out a reset
F265
Measurement function
disturbed
Program sequence of the measuring func-
tion disturbed
Device restarts automatically
Failure