5 Setup

VEGAFLEX 80 series • 4 … 20 mA/HART - two-wire

42960-EN-140924

5 Setup

5.1  General information

Take note of the mounting and installation instructions in the operating 

instructions manual.

When locking the adjustment, the instrument checks the data of the 

measurement loop and decides on the basis of the evaluation results 

if it is necessary to check the level.
Hence the following actions must be carried out at the time of every 

startup:

• 

Unlock adjustment

• 

if necessary, change parameters

• 

Lock adjustment and verify modified parameters, if necessary

5.2  Instrument parameter adjustment

The following adjustment units are permitted for parameterization of 

the safety function:

• 

Display and adjustment module

• 

The DTM suitable for VEGAFLEX 80 in conjunction with an 

adjustment software according to the FDT/DTM standard, e. g. 

PACTware

• 

The device description EDD suitable for VEGAFLEX 80

The parameter adjustment is described in the operating instructions 

manual.

The documentation of the device settings is only possible with the full 

version of the DTM Collection.

For protection against unwanted or unauthorzed adjustment, the set 

parameters must be protected against unauthorized access. For this 

reason, the instrument is shipped in locked condition. The PIN in 

delivery status is "0000".
The default values of the parameters are listed in the operating in-

structions. When shipped with customer-specific parameter settings, 

the instrument is accompanied by a list of the values differing from the 

default values.
By means of the serial number this list can also be downloaded at 

www.vega.com

/VEGA Tools/serial number search

.

To avoid or detect possible errors during parameter adjustment for 

unsafe operating environments, a verification procedure is used that 

allows the safety-relevant parameters to be checked.
Parameter adjustment proceeds according to the following steps:

• 

Unlock adjustment

• 

Change parameters

• 

Lock adjustment and verify modified parameters

The exact process is described in the operating instructions.

Mounting and installation

Function test

Tools

Safety-relevant param-

eters

Safe parameterization

Содержание VEGAFLEX 80

Страница 1: ...Safety Manual VEGAFLEX 80 series 4 20 mA HART two wire With SIL qualification Document ID 42960...

Страница 2: ...tics 4 1 Key figures acc to IEC 61508 6 4 2 Figures according to ISO 13849 1 6 4 3 Supplementary information 6 5 Setup 5 1 General information 8 5 2 Instrument parameter adjustment 8 6 Diagnostics and...

Страница 3: ...ale Sicherheit ist verf gbar in den Sprachen Deutsch Englisch Franz sisch und Russisch EN The current Safety Manual for Functional Safety is available in German English French and Russian language FR...

Страница 4: ...afety instrumented system according to IEC 61508 in the modes low demand mode and high demand mode Up to SIL2 in a single channel architecture Up to SIL3 in a multiple channel architecture The followi...

Страница 5: ...he safety function and the characteristics set on the sensor Character istics Monitoring upper limit val ue Monitoring lower limit value 4 20 mA Output current Switching point Output current Switching...

Страница 6: ...3849 1 Derived from the safety related characteristics the following figures result according to ISO 13849 1 machine safety 6 Parameter Value MTTFd 47 years DC 93 Performance Level 1 58 x 10 7 1 h cor...

Страница 7: ...ected control and processing unit must have the following properties The output circuit of the transmitter is judged according to the idle current principle fail low and fail high signals are interpre...

Страница 8: ...nual The documentation of the device settings is only possible with the full version of the DTM Collection For protection against unwanted or unauthorzed adjustment the set parameters must be protecte...

Страница 9: ...st be considered as unreliable This applies until the parameters are verified and the adjustment is locked again If the parameter adjustment process is not carried out completely the device statuses d...

Страница 10: ...he type of fault is outputted The fault messages are listed in the operating instructions 6 2 Repair If faults are detected the entire measuring system must be shut down and the process held in a safe...

Страница 11: ...st the safety function must be treated as unreli able Take into account that the function test influences downstream connected devices If necessary you must take other measures to maintain the safety...

Страница 12: ...test in the menu Diagnosis on the adjustment unit 3 Carry out the function test according to the operating instructions just like during initial operation To 1 Output signal corresponds to the level D...

Страница 13: ...last function test Test reason Test scope Setup without function test Setup with function test Proof test without function test Proof test with function test Mode Overflow protection Dry run protecti...

Страница 14: ...safe detected failure SU Rate for safe undetected failure S S SD SU DD Rate for dangerous detected failure DU Rate for dangerous undetected failure H Rate for failure who causes a high output current...

Страница 15: ...15 10 Supplement C SIL conformity VEGAFLEX 80 series 4 20 mA HART two wire 42960 EN 140924 10 Supplement C SIL conformity...

Страница 16: ...16 10 Supplement C SIL conformity VEGAFLEX 80 series 4 20 mA HART two wire 42960 EN 140924...

Страница 17: ...17 Notes VEGAFLEX 80 series 4 20 mA HART two wire 42960 EN 140924...

Страница 18: ...18 Notes VEGAFLEX 80 series 4 20 mA HART two wire 42960 EN 140924...

Страница 19: ...19 Notes VEGAFLEX 80 series 4 20 mA HART two wire 42960 EN 140924...

Страница 20: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: