7 Diagnostics and servicing
VEGACAP 65 • Two-wire
30019-EN-230510
70 mm (2.76"
)
200 mm
(7.87"
)
Fig. 19: Take the gravity weight into account and shorten the cable respectively
5. Shift the gravity weight again flush to the cable and fix it with the
two pins.
6. Mount the probe into the vessel. Make sure that the probe is
uncovered.
2
1
Fig. 20: Compensation key
1 Measuring range selection switch (compensation key)
2 Control lamp
7. Keep the measuring range selection switch (1) pushed until the
control lamp (2) flashes green.
8. Hence the probe is compensated to the modified length.
9. Carry out the adjustment again. See chapter "
Set-up, adjustment
elements
".
7.5 How to proceed if a repair is necessary
You can find an instrument return form as well as detailed information
about the procedure in the download area of our homepage. By doing
this you help us carry out the repair quickly and without having to call
back for needed information.
Proceed as follows in case of repair:
•
Print and fill out one form per instrument
•
Clean the instrument and pack it damage-proof