27
6 Supplement
MINITRAC 31 • Foundation Fieldbus
62076-EN-190704
6 Supplement
6.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions which are included in delivery are valid for
approved instruments (e.g. with Ex approval). These data can differ from the data listed herein, for
example regarding the process conditions or the voltage supply.
Electromechanical data - version IP 66/IP 67
Cable entry
Ʋ M20 x 1.5
2 x cable gland M20 x 1.5 (cable: ø 6 … 12 mm), 4 x
blind plug M20 x 1.5
Included: 1 x cable gland M20 x 1.5
Ʋ ½ NPT
5 x closing cap (red) ½ NPT
Included: 3 x cable gland ½ NPT (cable: ø 6 … 12 mm),
4 x blind plug ½ NPT
Spring-loaded terminals for wire cross-section
Ʋ Massive wire, stranded wire
0.2 … 2.5 mm² (AWG 24 … 14)
Ʋ Stranded wire with end sleeve
0.2 … 1.5 mm² (AWG 24 … 16)
Voltage supply
Operating voltage
Ʋ Sensor power supply
20 … 72 V DC or 20 … 253 V AC, 50/60 Hz
Ʋ FF bus
9 … 32 V DC