D4 Post Top Retrofit Kit 

INSTALLATION GUIDE  

 
 
  
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

PLEASE READ ALL INSTRUCTIONS BEFORE ATTEMPTING INSTALLATION 

                                                                                             

WARNING

!

 

 

RISK OF FIRE OR ELECTRIC SHOCK. INSTALLATION OF THIS RETROFIT ASSEMBLY REQUIRES  A PERSON 
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE LUMINAIR

E’S ELECTRICAL SYSTEM. IF NOT 

QUALIFIED, DO NOT ATTEMPT INSTALLATION. CONTACT A QUALIFIED ELECTRICIAN. 

 

RISK  OF  FIRE  OR  ELECTRIC  SHOCK.  INSTALL  THIS  KIT  ONLY  IN  THE  LUMINAIRES  THAT  HAS  THE 
CONSTRUCTION  FEATURES  AND  DIMENSIONS  SHOWN  IN  THE  PHOTOGRAPHS  AND/OR  DRAWINGS  AND 
WHERE  THE  INPUT  RATING  OF  THE  RETROFIT  KIT  DOES  NOT  EXCEED  THE  INPUT  RATING  OF  THE 
LUMINAIRE. 

 

RISK  OF  FIRE  OR  ELECTRIC  SHOCK.  LUMINAIRE  WIRING  AND  ELECTRICAL  PARTS  MAY  BE  DAMAGED 
WHEN DRILLING FOR INSTALLATION OF LED RETROFIT KIT. CHAECK FOR ENCLOSED WIRING AND PARTS. 

 

ONLY  THOSE  OPEN  HOLES  INDICATED  IN  THE  PHOTOGRAPS  AND/OR  DRAWINGS  MAY  BE  MADE  OR 
ALTERED  AS  A  RESULT  OF  KIT  INSTALLATION.  DO  NOT  LEAVE  ANY  OTHER  OPEN  HOLES  IN  AN 
ENCLOSURE OF WIRING OR ELECTRICAL COMPONENTS. 

 

DO  NOT  MAKE  OR  ALTER  ANY  OPEN  HOLES  IN  AN  ENCLOSURE  OF  WIRING  OR  ELECTRICAL 
COMPONENTS DURING KIT INSTALLATION. 

 

TO PREVENT WIRING DAMAGE OR  ABRASION, DO NOT EXPOSE WIRING TO EDGES OF SHEET METAL OR 
OTHER SHARP OBJECTS. 

 

THIS  RETROFIT  KIT  IS  ACCEPTED  AS  A  COMPONENT  OF  A  LUMINAIRE  WHERE  THE  SUITABILITY  OF  THE 
COMBINATION SHALL BE DETERMINED BY AUTHORITIES HAVING JURISDICTION.

  

 

 

 

 

 

 

RISQUE D’INCENDIE OU DE CHOC ÉLECTRIQUE. L’INSTALLATION DE CE NÉCESSAIRE DE MODERNISATION 
EXIGE  UNE  PERSONNE  FAMILIÈRE  AVEC  LA  CONSTRUCTION  ET  LE  FONCTIONNEMENT  DU  SYSTÈME 
ÉLECTRIQUE  DU  LUMINAIRE  ET  DES  RISQUES  ASSOCIÉS.  TOUTE  PERS

ONNE  QUI  N’EST  PAS  QUALIFIÉE 

NE DOIT FAIRE AUCUNE 

TENTATIVE D’INSTALLATION ET DOIT CONTACTER UNE PERSONNE QUALIFIÉE. 

 

RISQUE  D’INCENDIE  OU  DE  CHOC  ÉLECTRIQUE.  N’INSTALLER  CE  NÉCESSAIRE  QUE  DANS  LES 
LUMINAIRES  DONT  LES  CARACTÉRISTIQUES  DE  CONSTRUCTION  ET  LES  DIMENSIONS  SONT  CONFORME 
À  CELLES  ILLUSTRÉES  DANS  LES  PHOTOS  ET/OU  LES  DESSINS  ET  DON

T  LA  PUISSANCE  D’ENTRÉE 

NOMINALE DU NÉCESSAIRE DE MODERNISATION NE DÉPASSE PAS CELLE DU LUMINAIRE. 

 

IL  EST  INTERDIT  DE  FAIRE  OU  DE  MODIFIER  UNE  OUVERTURE  DANS  UN  BOÎTIER  DE  CÂBLAGE  OU  DE 
COMPOSANTS ÉLECTRIQU

ES AU COURS DE L’INSTALLATION DU NÉCESSAIRE. 

 

AFIN  DE  PRÉVENIR  L’ENDOMMAGEMENT  OU  L’ABRASION  DES  CÂBLES,  ÉVITER  TOUT  CONTACT  ENTRE 
CES DERNIERS ET LE B

ORD D’UN OBJET TRANCHANT TEL QU’UNE TÔLE. 

 

LE NÉCESSAIRE DE MODERNISATION EST ACCEPTÉ À TITRE DE COMPOS

ANT D’UN LUMINAIRE LORSQUE 

LA PERTINENCE DE LA COMBINAISON DOIT ËTRE DÉTERMINÉE PAR PAR LES AUTORITÉS COMPÉTENTES 

The D4 Post Top Retrofit Kits from Vega Light Control Systems 

 

Designed as an easy and reliable way to convert existing fixtures  

 

Alternative to HID lamps, up to 300W MH and 200W HPS 

 

Use for pole heights up to 30 feet 

 

Eliminates mercury & lead 

 

Reduce carbon footprint & light pollution.  

 

Tested to the most demanding industry standards:  

o

 

LM-79, LM-80, In-Situ, TM-21, and DLC 

o

 

surge testing to UL 1449 3rd edition  

o

 

UL 1598C 1st Ed. and CSA TIL B-79A 

INS-00690-01 20181028 

AVERTISSEMENT

 

 

Содержание D4-F

Страница 1: ...TION RISQUE D INCENDIE OU DE CHOC ÉLECTRIQUE L INSTALLATION DE CE NÉCESSAIRE DE MODERNISATION EXIGE UNE PERSONNE FAMILIÈRE AVEC LA CONSTRUCTION ET LE FONCTIONNEMENT DU SYSTÈME ÉLECTRIQUE DU LUMINAIRE ET DES RISQUES ASSOCIÉS TOUTE PERSONNE QUI N EST PAS QUALIFIÉE NE DOIT FAIRE AUCUNE TENTATIVE D INSTALLATION ET DOIT CONTACTER UNE PERSONNE QUALIFIÉE RISQUE D INCENDIE OU DE CHOC ÉLECTRIQUE N INSTALLE...

Страница 2: ...N FIXTURE AMBIENT OPERATING TEMPERATURE FOR LED RETROFIT MODULE 104 F 40 C MAXIMUM AMBIENT OPERATING TEMPERATURE CANNOT EXCEED 140 F 60 C INSTALLATION REQUIREMENTS MAY VARY DEPENDING ON THE LUMINAIRE RETROFITTED IF UNCERTAIN CONTACT VEGA LIGHT CONTROL SYSTEMS CUSTOMER SERVICE TO EVALUATE APPLICABILITY TO FIXTURE SUPPORT VEGALIGHTCONTROL COM PHONE 616 259 0700 1 PRODUCT OVERVIEW 1 1 D4 Post Top Ret...

Страница 3: ...pplication Specific configuration for mounting in Granville Classic 7 and 4 fitters with 19 glass globes One piece assembly Granville Premier Kit Style Watts CCT Type Mounting Dimming Mounting Code Details D4 H 30 22K T5M CGPCS STD Granville Premier w Photo Control Socket D4 H 40 30K T3M NA CGPNS DIM Granville Premier w o Photo Control Socket D4 H 60 40K H PXYZ H prefix is high output version 80 N...

Страница 4: ...0 mm LED Light Engine Height Adjustable From 15 Down To 9 75 D4 F Model Fully Enclosed 60W Max Adapter Plate D4 S Down Light Model with Side Brackets D4 M Model Mid Mount Enclosed 80W Max 4 73 or 5 91 120 or 150 mm Height Adjustable From 11 Down To 9 75 Connected by 24 Cable w Connectors 6 6 167 mm 4 5 115 mm D4 C Model Socket Replacement 4 73 or 5 91 120 or 150 mm 6 6 167 mm 4 5 115 mm Extrusion ...

Страница 5: ... LexaLite Lindy 408 globe performs best at LED height set 8 from the base of the globe Crown 88266 CL has an optimum output when set 13 from the base of the globe 5 Measure the maximum temperature achieved at the locations shown below after at least 2 hours under power inside fixture Take that temperature and add the difference between room temperature and 40C to calculate the maximum Tc For examp...

Страница 6: ...before servicing WARNING Risk of burn Allow unit to cool fully before servicing POST TOP Note Failure to remove original components including ballast will void product warranty Original optical components reflectors Fixture Dome Top Ballast Socket Lamp Fixture Base Fixture Globe Note Kits are available for specific targeted luminaries Holophane Granville Premier cat No GVP Granville Classic cat No...

Страница 7: ...ight tighten set screw enough to hold tube then tighten another turn with hex key see 1 4 2 4 Side brackets can be adjusted bent trimmed or special ordered to span or offset LED mounting height Allow adequate space around all sides of LED Light Engine from fixture or globe see 1 4 5 Order a lower wattage of kit if install is still exceeding Tc limits with LED kit properly positioned Assembled Retr...

Страница 8: ...facing the street see 1 4 6 Re use screws previously holding HID ballast to fixture to attach Retrofit Kit when possible Additional hardware maybe required For Post Top fixtures LED Light should be installed to maintain cooling clearance above heatsink and at arc tube height of replaced HID see 1 4 5 Restore the original light fixture sealing for water and insect control Rain water must not enter ...

Страница 9: ... Black or Blue using pre installed Lever Nuts If photocell controlled or remote controlled connect Retrofit Kit to output of the control 2 5 STEP 5 Secure fixture components Secure fixture components and restore original light fixture sealing for water and insect control Notes Additional hardware maybe required to mount LED Retrofit Kit in fixture Re use screws previously holding HID ballast to fi...

Страница 10: ...arranty period contact VEGA sales representative for RMA 3 If out of warranty period contact VEGA sales representative for information to replace surge protector LEDs are dim or not lit 1 DC Cable is unplugged 2 Power supply has failed 3 LED board is damaged 1 Connect the DC Cable by plugging together the two Molex connectors 2 To identify failed power supply use clamp meter tongs to measure outpu...

Отзывы: