Vega TP-11 / User Manual
24
Revision 09 – 08 April 2020
When measurements are out of specified current value range the communication
period still the same if parameter “Immediately send data when current is out of range” is not
active.
If that parameter is active and external power supplying, then the alarm message will
be forming and sending during 2 minutes after the moment of current value measurements
are out of specified range. If external power not supplying, then the converter will detect
exceeding the specified limits during the following data collection session according the
schedule only, but the modem will send that data immediately too. Every following message,
which will form according to the data collection period, also will have sent immediately until
the current value measurements are back in range.
The readings are read from the connected device at 00.00 on the internal clock of the
device if the data collection period is set to 24 hours, at 00.00 and at 12.00, if the period is 12
hours and so on. All readings are stored in the device memory until the next communication
session. The data transfer period can be adjusted from 5 minutes to 24 hours. Data transfer is
carried out by a random time at the selected period. At the next communication session, the
device starts sending accumulated packets with readings, from the earliest to the latest.
With the "Confirmed uplinks" option turned on, the device will send the next packet only
after receiving a confirmation of the delivery of the previous one. If such confirmation has not
received after the fulfilled in the settings uplink number of transmission, device completes the
communication session until the next one according to the schedule. In this case, the device
continues to collect data according to the data collection period and store it in memory. Non-
transmitted packets remain in the device memory until the next communication session.
With the "Confirmed uplinks" option turned off, the device just sends all accumulated
packets to the network in order from the earliest to the latest. There are no checks of package
delivery in this mode. There are no non-transmitted messages in the device memory.
Data collection period when measurements are out of specified current value range set
independently and may be equal from 5 minutes to 24 hours.
External sensor settings
– allows to set the startup time for external sensor supply.
Startup time value can be varying from 1 to 60 seconds.