OX-MPO-12 Switch Reference Card 

Evaluating MPO-SM Connectors with FX150+ OTDRs (other OTDRs TBD) 

 

Month 2020 | D08-00-XXX Rev. XXX  

     ©2020 VeEX Inc. All rights reserved.

 

www.veexinc.com 

This quick guide provides setup instructions to perform MPO OTDR fiber testing using an FX150+/FX150 OTDR and VeEX 

OX-MPO-12 Switch. It is assumed that the user is familiar with VeEX OTDR setup and trace analysis functions discussed in 

the OTDR series manual.  

Setup Materials: 

Description 

Quantity 

Notes: 

FX150+/FX150 OTDR 

1x 

Needs Latest GA release software (1.00.4912 or up). See About Page to check. 

OX-MPO-12 Switch 

1x 

No comment 

Micro-USB (B) to Micro-USB (B) 

1x 

Provided with purchase of OX-MPO-12 Switch, required for FX150+/FX150 

OTDR to control OX-MPO-12 Switch  

SC/APC - SC/APC (1m) patch cord 

1x 

Connection transforms a simplex OTDR port into multifiber OTDR. 

OX-MPO-12 Test Cable Kit 

1x 

Upon price quote/purchase option 

MPO launch and receive cables 

1x launch, 
1x receive 

User-supplied, if OX-MPO-12 Test Cable Kit was not purchased. 

Figure 1: Test Setup Combinations (not all shown) 

General Setup Instructions: (Steps 1 to 4, refer to Figure 1) 

1. After gathering all required materials mentioned in the table, boot up the FX150/FX150+ OTDR. If FX150/FX150+ is

already booted up with OTDR application open and MPO switch is disconnected, exit out of the active application

to Home menu. (Figure 1)

2. Connect one end of the Micro-USB (B) to Micro-USB (B) cable from the FX150/FX150+ OTDR port to the OX-MPO-

12 Switch port.

3. Attach one end of the 1 m 

SC-APC to SC-APC simplex patch cord

 from the OTDR port (SC-APC) to the SC-APC port

of the switch.

4. Attach either one of three cases to the MPO output port of the OX-MPO-12 Switch

a. MPO/APC to MPO/UPC hybrid cable for launch cable, and MPO/UPC cables for FUT (Fiber under test) and

receive cable. Alternately, another MPO/APC to MPO/UPC hybrid cable can be used at the receive end.

b. MPO/APC ends for launch cable, FUT, and receive cable.