RS-232 Commands
Function Code: 606
39
Function Code: 606
Function Type:
Set Tank 20 Point Full, 95%, 90%,... Volumes
Version 1
Command Format:
Set:
Inquire
:
Display:
<SOH>S606TTGGGGGGggggggGGGGGGgggggg...
Display:
<SOH>I606TT
or:
<SOH>S606TTGGGG,gggg,GGGG,...
Computer:
<SOH>
s606TFFFFFFFF...
Computer:
<SOH>i606TT
Notes:
1.
TT - Tank Number (Decimal, 00=all)
2.
GGGGGGgggggg
- Series of 20 Volumes, Gallons (Decimal)
3.
FFFFFFFF
- Series of 20 Volumes, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I606TT
JAN 22, 1996 3:16 PM
TANK 20 POINT VOLUMES
TANK
PRODUCT LABEL
GALLONS
1
REGULAR UNLEADED
9720
9234
8748
8262
7776
7290
6804
6318
5832
5346
4860
4372
3888
3402
2916
2430
1944
1458
972
486
<ETX>
Typical Response Message, Computer Format:
<SOH>i606TT0000000000TTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1.
0000000000
- Not Used.
2.
TT - Tank Number (Decimal, 00 = all)
3.
FFFFFFFF
- Series of 20 Volumes, Gallons (ASCII Hex IEEE float)
4.
&&
- Data Termination Flag
5.
CCCC - Message
Checksum