6
Communications Setup
Auto-Transmit Setup (RS-232 or RS-232/RS-485 Modules Only)
6-6
•
AUTO HIGH WATER LIMIT
• AUTO OVERFILL LIMIT
•
AUTO LOW PRODUCT
• AUTO THEFT LIMIT
•
AUTO DELIVERY START
• AUTO DELIVERY END
•
AUTO EXTERNAL INPUT ON
• AUTO EXTERNAL INPUT OFF
•
AUTO SENSOR FUEL ALARM
• AUTO SENSOR WATER ALARM
•
AUTO SENSOR OUT ALARM
When you have finished selecting Auto Transmit for the above items, press STEP until you see TRANSMIT
MESSAGE SETUP message.
AUTO DELAY TIME
Press STEP in response to the TRANSMIT MESSAGE SETUP message. The system displays the message:
NOTE: The above message appears only if you chose Transmit for at least one of the items in the step described
above.
Use this display to specify the time interval between any alarm, delivery, or input indication in the system and the
time the system sends an Auto-Transmit message. To set the Auto Delay Time, press CHANGE and enter the
delay time, in seconds, up to a maximum of 254 seconds. Press ENTER to confirm your entry. The system
displays:
Press STEP to continue.
AUTO REPEAT TIME
After you set the Auto Delay Time, the system displays the message:
NOTE: The above message appears only if you chose Transmit/Repeat for at least one of the items in the steps
described above.
Use this display to specify the length of time the system waits before retransmitting a message. To set the Auto
Repeat Time, press CHANGE and enter the repeat time, in seconds, up to a maximum of 240 seconds
.
Press
ENTER to confirm your entry. The system displays:
CONTINUE COMMUNICATIONS SETUP
Press STEP to return to the AUTO TRANSMIT SETUP message. Press STEP again to continue to the next
communications setup function.
AUTO TRANSMIT MESSAGE
AUTO DELAY TIME: 005
AUTO DELAY TIME: XXX
PRESS <STEP> TO CONTINUE
AUTO TRANSMIT MESSAGE
AUTO REPEAT TIME: 060
AUTO REPEAT TIME: XXX