6-5
6
Communications Setup
Auto-Transmit Setup (RS-232 or RS-232/RS-485 Modules Only)
This feature allows the user to program the S-Sat Module’s Data Transmit Ready (DTR) normal state to either High
or Low. The default state is High. Press CHANGE and ENTER to select the Low state, or press STEP to accept
the default state and continue.
SPECIFYING PORT SETTINGS FOR ADDITIONAL COMMUNICATION MODULES
After you set the last port setting, the system returns to the PORT SETTINGS message. If you have additional
communication modules to set up, press ENTER to display the BAUD RATE message, press TANK/SENSOR to
choose another communication module and then repeat the procedure described above to enter port settings for
the selected module.
CONTINUE COMMUNICATIONS SETUP
When you have specified port settings for all the communication modules, press STEP in response to the PORT
SETTINGS message to advance to the next communications setup function.
Auto-Transmit Setup
(RS-232 or RS-232/RS-485 Modules Only)
If necessary, press STEP until you see the message:
The Auto-Transmit Setup feature allows you to set an Automatic Transmit or Transmit/Repeat of any of the
following signals – in-tank alarm, sensor alarm, delivery start/stop, and input on/off – to an external device via the
RS-232 or RS-485 port.
If you enable this feature, the system provides three choices for each type of alarm, delivery, or input feature
configured in the system. These choices are: Disable, Transmit, Transmit/Repeat. If you choose Transmit or
Transmit/Repeat for any alarm, delivery, or input message, you must enter an Auto-Transmit Delay Time. In addition,
if you choose Transmit/Repeat for any item, you must enter an Auto-Transmit Repeat Time.
NOTE: The entered Delay and Repeat times apply to all transmit and repeat choices.
AUTO-TRANSMIT METHOD
Press ENTER in response to the AUTO TRANSMIT SETUP message. The system displays the message:
Press ENTER to continue. The system displays:
Use this display to choose Auto Transmit for the Auto Leak Alarm Limit. To choose DISABLED, press STEP. To
choose Transmit, press CHANGE once in response to the AUTO LEAK ALARM LIMIT message. To choose
TRANSMIT/REPEAT, press CHANGE twice. Press ENTER to confirm your choice. The system displays:
Repeat the above steps to continue selecting Auto Transmit for the remaining alarm, delivery, or input signals:
AUTO TRANSMIT SETUP
PRESS <ENTER>
TRANSMIT MESSAGE SETUP
PRESS <ENTER>
AUTO LEAK ALARM LIMIT
DISABLED
(Selected Setting)
PRESS <STEP> TO CONTINUE