5
System Setup
Tanker Load Report - International Option
5-14
To enter a different TC reference temperature, press CHANGE. Enter a value between 0 and 120°F (-17 to
+49°C). Press ENTER to confirm your entry. The system displays:
Tanker Load Report -
International Option
The Tanker Load Report is an optional feature. In the ENABLE position, a report is printed after every tanker load is
dispensed.
Press STEP to display the message:
Press CHANGE to select DISABLE, then ENTER to not automatically print this report. See the Operating Mode
charts in the Operator’s Manual to print out a report when you want it.
Stick Height Offset -
International Option
The Stick Height Offset is a “reference only” height reading that allows a user- programmable offset to be entered
that makes the probe height reading “appear” to be the same as the stick height reading. Stick height offset will
not be used for volume calculation. If this feature is enabled, you must enter the stick height offset for each tank in
the In-Tank Setup section of this manual (“Stick Offset (International Option)” on page 7-24).
Press STEP to display the message:
Press CHANGE, ENTER, then STEP to enable this feature, or Press STEP to leave it disabled and continue.
Ullage
Tank Ullage can be changed from the default value of 90 percent to 95 percent as required.
Press STEP to display the message:
Press CHANGE, ENTER, then STEP to select 95%, or Press STEP to leave it at 90% and continue.
H-Protocol Data Format -
International Option
This feature is available only if there is an RS-232 or modem module installed in the console and H-protocol is
used.
VALUE (DEG F): +(TC Value)
PRESS <STEP> TO CONTINUE
TANKER LOAD REPORT
ENABLE
STICK HEIGHT OFFSET
DISABLED
ULLAGE
90 PERCENT