24
Output Relay Setup
Relay Designation
24-2
Press STEP. If more than one module is installed, the system automatically advances to the RELAY CONFIG
message for the next module. Up to 8 modules may be installed. Repeat the steps described above for each
module until you have entered the configuration information (relay positions) for all modules and the system
displays the ENTER RELAY DESIGNATION message.
Relay Designation
If necessary, press STEP until you see the message:
Enter the name of the device connected to the selected output relay. Typical names are: OVERFILL ALARM;
AUTO DIALER; etc. (This name appears on reports to make it easier to identify the external device. The name also
appears on the display when in-tank or sensor alarms and external inputs are assigned to the relay).
To enter a designation for the selected relay, press CHANGE and enter up to 20 alphanumeric characters. Press
ENTER to confirm your entry. The system displays:
Press STEP to continue.
Selecting Relay Type
If necessary, press STEP until you see the message:
From this display, press CHANGE to display one of four output relay types:
•
STANDARD - The On/Off state is determined by assigned alarms/warnings.
•
PUMP CONTROL OUTPUT - Responds to a pump request received from an assigned Pump Sense module or
Line Leak module.
•
MOMENTARY - The On/Off state is determined by assigned alarms/warnings. However, relay returns to the
inactive state after the ALARM/TEST key is pressed to acknowledge the alarm.
•
PUMP COMM CONTROL - Select this relay type only when a set of line manifolded tanks are using Red Jacket
IQ Controllers, and you want to run PLLD/WPLLD precision line leak tests. After selecting this relay type, when
one IQ controlled pump of a manifolded set is turned On for line leak testing, the relay will activate, blocking
communication with the second IQ controlled pump (giving the console total control of the pumps) until the
precision test is complete.
When the desired relay type appears on the display, press ENTER to confirm your choice.
If you select STANDARD or MOMENTARY, the display reads:
To accept normally open (relay de-energized when alarm is inactive), press STEP. Press CHANGE to display
normally closed (relay energized when alarm is inactive), then ENTER to accept.
ENTER RELAY DESIGNATION
R1:
R1: (Name)
PRESS <STEP> TO CONTINUE
R1: SELECT RELAY TYPE
STANDARD
R X:SELECT ORIENTATION
NORMALLY OPEN