17-1
17
Reconciliation Setup
To select Reconciliation Setup, press FUNCTION until you see the message:
Press STEP to continue.
International installations - for consoles without BIR, the HRM Features DIP switch (see “TLS-350 Consoles” on
page 4-1) must be enabled to enter Reconciliation Setup.
Dispenser Module Data String
If necessary, press STEP until you see the message:
Device codes for the two types of DIM modules are a “M” for Mechanical Dispenser Interface Modules (MDIM),
and an “E” for Electronic Dispenser Interface Modules (EDIM). All EDIM modules install in the Comm Bay of the
console and include; Current Loop, Block, RS-232, IFSF, and RS-485 dispenser interface modules. All MDIM
modules install in the Power Bay of the console and include; Low Voltage Mechanical, and High Voltage
Mechanical Dispenser Interface Modules.
When a BDIM, EDIM, or CDIM is installed, the system will recognize its presence and position in the Comm Bay
of the console. When a MDIM is installed, the system will recognize its presence and position in the Power Bay.
To enter a dispenser module data string, press CHANGE, enter a valid DIM description selected from the
appropriate DIM Installation Manual. The system accepts up to twelve alphanumeric characters; however, it reads
only the first eight. If no data are entered, the DIM defaults are used.
After entering your description, press ENTER. The system confirms your entry with the following message:
If more than one DIM is installed, the system will automatically advance to the next module when setup for one is
complete. You can also press TANK/SENSOR to select a specific module. When all DIM modules have been set
up, press STEP to advance to the next feature. (The system displays the AUTOMATIC DAILY CLOSING
message.)
Automatic Daily Closing
If necessary, press STEP until you see the message:
Enter the time you wish to designate as the daily closing time. At the programmed time, the system stores the
current day’s data, and prints a report if “Daily BIR Reports” was set to enabled in System Setup (page 5-5). The
default time is set to 2:00 a.m. This feature cannot be disabled.
RECONCILIATION SETUP
PRESS <STEP> TO CONTINUE
DISP. MODULE DATA STRING
EDIM #X: XXXXXXXX
XDIM#X: [Description]
PRESS <STEP> TO CONTINUE
AUTOMATIC DAILY CLOSING
TIME: 2:00 AM