11
Wireless Pressurized Line Leak Detection
Tank Selection
11-6
ENTERING THE PRESSURE OFFSET VALUE FOR EACH TRANSDUCER
Press MODE to return to the SETUP MODE, then FUNCTION until you see the message:
Press STEP until you see the message:
Press CHANGE and enter the Pressure Offset value for transducer W1. If necessary, press the left arrow key to
change the sign (+ or -). Note: enter the Offset value
exactly
as displayed in the Offset test result message
(inc or - sign). Press TANK/SENSOR, to display another transducer. Press CHANGE to enter its Pressure
Offset value, then ENTER to confirm the change. Repeat this procedure until you have entered Offsets for all
transducers.
Tank Selection
This entry allows a tank’s WPLLD to act as a pump sense input for automatic in-tank leak detection, CSLD,
catastrophic leak testing and other features. This step can only be used for tanks that are not already connected to
a line leak detector. This message appears
only
if tanks have been configured in the In-Tank Setup procedure.
For no selection press STEP to continue. If yes, press CHANGE until the tank number to which the particular
WPLLD is connected appears, then press ENTER. The system confirms your choice with the message:
Press STEP to continue.
Selecting a Dispense Mode
NOTE: This option will only appear if a tank has been selected for the WPLLD.
If necessary, press STEP until you see the message:
This entry asks you to select the dispense mode. You can select between:
•
STANDARD - Only one pump feeds the line.
WPLLD LINE LEAK SETUP
PRESS <STEP> TO CONTINUE
W 1: WPLLD NUMBER 1
PRESSURE OFFSET: +XX.X
W1: SELECT TANK
NONE
T#: (Product Label)
PRESS <STEP> TO CONTINUE
W1: ENTER DISPENSE MODE
XXXXXXXXX