8-7
8
In-Tank Leak Tests
Gross Test Auto-Confirm
Gross Test Auto-Confirm
If necessary, press STEP until you see the message:
Note: this message only displays if you have selected CSLD as the test frequency and the tank is assigned to a
pump sensing device (any LLD, pump sense, I/O).
If you are experiencing tank gross test alarms that are proven to be false, enabling this feature may reduce these
false alarms. When enabled, two test fails in a row will be required before a Fail is posted. However, when enabled
this feature will also increase the time needed to detect a gross leak by one 30-45 minute idle period.
To leave this feature disabled, press STEP to continue, or press CHANGE, then ENTER and the message
displays:
Press STEP to continue.
Leak Test Start Time
If necessary, press STEP until you see the message:
You can enable the test by entering a start time or leave the test disabled.
To leave the test disabled, press STEP. (The system displays the TEST RATE message.)
To enter a start time, press CHANGE in response to the START TIME message. Enter the start time and press the
Right Arrow key to select AM or PM. Press ENTER to confirm your entry:
Press STEP to continue.
Leak Test Rate
If necessary, press STEP until you see the message:
You can set the leak test rate at 0.2 gph or 0.1 gph (0.76 lph or 0.38 lph). The default test rate is 0.2 gph. The
system prints a leak report at the completion of the test.
NOTE: The 0.1 gph option appears only when a 0.1 gph Mag probe is installed.
To accept the default rate of 0.2 gph, press STEP. (The system displays the TEST DURATION message.)
GROSS TEST: ALL TANK
AUTO-CONFIRM: DISABLED
GROSS TEST: ALL TANK
AUTO-CONFIRM: ENABLED
START TIME: ALL TANK
TIME: DISABLED
TIME: XX:XX XM
PRESS <STEP> TO CONTINUE
TEST RATE: ALL TANK
0.10 GAL/HR