Introduction
Specifications
11
Distance between centerline of UMP and centerline of bottom fill tube should be 3 feet (914
mm) minimum. Air locking of pump after product delivery may occur at distances less than
this.
Specifications
Table 2 shows the adjustable pump lengths by model
Table 3 shows pump electrical service requirements.
Table 4 lists UMP weights and lengths and Table 5 lists pump shut off pressures.
Table 2. Distances From Top Of Lifting Screw To Inlet
Model#
Retracted
Extended
in.
mm
in.
mm
AGP75S17-3RJ1, P75U17-3RJ1
73.0
1853
103.5
2624
AGP75S17-3RJ2, P75U17-3RJ2
103.0
2615
163.5
4148
AGP75S17-3RJ3, P75U17-3RJ3
163.0
4139
223.5
5672
AGP150S17-3RJ1, P150U17-3RJ1
75.0
1903
105.5
2674
AGP150S17-3RJ2, P150U17-3RJ2
105.0
2665
165.5
4198
AGP150S17-3RJ3, P150U17-3RJ3
165.0
4189
225.5
5722
X4AGP150S17RJ1, X4AGP150U17RJ1
75.5
1917
106.0
2688
X4AGP150S17RJ2, X4AGP150U17RJ2
105.5
2679
166.0
4212
X4AGP150S17RJ3, X4AGP150U17RJ3
165.5
4203
226.0
5736
AGP200S17-4RJ1, P200U17-4RJ1
77.5
1975
108.0
2745
AGP200S17-4RJ2, P200U17-4RJ2
107.5
2735
168.0
4270
AGP200S17-4RJ3, P200U17-4RJ3
167.5
4260
228.0
5790
Table 3. Electrical Service Information
Required power supply rating for 3 phase pumps, required rating is 380 - 415 Vac.
UMP Model No.
HP
Hz
PH
Voltage
Fluctuation
Range
Max.
Load
Amps
Locked
Rotor
Amps
Winding Resistance (Ohms)
Setting on Motor
Protection Device
Min.
Max.
Black-
Orange
Red-
Orange
Black-Red
AGUMP75S17-3,
UMP75U17-3
3/4
50
3
342
457
2.2
8.1
24.4 - 29.6
24.4 - 29.6
24.4 - 29.6
1.8
AGUMP150S17-3,
UMP150U17-3
1-1/2
50
3
342
457
3.8
14.1
12.1 - 14.7
12.1 - 14.7
12.1 - 14.7
3.8
X4AGUMP150S17,
X4UMP150U17
1-1/2
50
3
342
457
3.8
14.1
12.1 - 14.7
12.1 - 14.7
12.1 - 14.7
3.8
AGUMP200S17-4,
UMP200U17-4
2
50
3
342
457
5.0
17.7
9.9 - 12.0
9.9 - 12.0
9.9 - 12.0
4.5
NOTICE