B-1
Appendix B: Vendor Information – Veeder-Root
The ProtoNode provides capability to support any Veeder-Root serial command by defining customized map
descriptors for any command or data type. Refer to Appendix A of the 577014-368 QuickServer Industrial Protocol
Gateway Installation And Setup manual. Appendix A (Security Code) of the same manual also contains instructions
on using a Security Code for the TLS communications port.
Interface To BACnet & Modbus Tables
An X in the BACnet Object ID or Modbus Register represents a one- or two-digit number that equals
the Node ID. In the Liquid Sensor X Fuel Alarm examples below, with a Node ID of 3, the X will be 3;
for a Node ID of 11, the X will be 11.
Table B-1. System Veeder-Root Interface To BACnet And Modbus
Table B-2. Unknown_Type Veeder-Root Interface Mappings To BACnet And Modbus
Point Name
Node ID
BACnet Object ID (X002)
Modbus Register (10X02)
Sensor X Fuel Alarm
3
3
002
10
3
02
Sensor X Fuel Alarm
11
11
002
10
11
02
Point Name
BACnet Object Type
BACnet Object ID
Modbus Register
Printer out of Paper
BI
1
10001
Printer Error
BI
2
10002
EEPROM Configuration Error
BI
3
10003
Battery Off
BI
4
10004
Too Many Tanks
BI
5
10005
System Security Warning
BI
6
10006
ROM Revision Warning
BI
7
10007
Remote Display Communications Error
BI
8
10008
Autodial Error
BI
9
10009
Software Module Warning
BI
10
10010
Tank Test Shutdown Warning
BI
11
10011
Protective Cover Alarm
BI
12
10012
BIR Shift Close Pending
BI
13
10013
BIR Daily Close Pending
BI
14
10014
PC(H8) Revision Warning
BI
15
10015
System Self Test Error
BI
16
10016
System Clock Incorrect Warning
BI
17
10017
System Device Poll Timeout
BI
18
10018
Maintenance Tracker NVMem
BI
19
10019
Maintenance Tracker Communication Module
BI
20
10020
Database Error
BI
21
10021
File System Error
BI
22
10022
BIR Status Warning
BI
23
10023
VR Bus Power Outage Warning
BI
24
10024
Software Upgrade Failure Alarm
BI
25
10025
iButton Fault Warning
BI
26
10026
iButton Fault Alarm
BI
27
10027
Version Upgrade Available
BI
28
10028
Expansion Box Unsupported
BI
29
10029
Point Name
BACnet Object Type
BACnet Object ID
Modbus Register
Unknown Device Address
AI
1
30001
Unknown Alarm Category
AI
2
30002
Unknown Alarm Type
AI
3
30003
NOTICE