Installation
Floating Suction Installation Information
16
Floating Suction Installation Information
Figure 7. Floating Suction Installation
Table 4. Electrical Service Information
HP
Volts
Phase
Service
Factor
Current
Locked
Rotor
Current
Branch Circuit
Protection
Wire Size for Max. Length of Run Shown
(From Service Entrance to Pump in Feet)
NEMA
Codes
Fusetron
Circuit.
Breaker
(Amps)
(Amps)
(Amps)
(Amps)
No. 14
No. 12
No. 10
No. 8
No. 6
3
208-230*
3
11.0
56.0
15
20
255
406
635
997
1552
J
3
380-415
3
5.4
25.0
15
15
787
1250
1956
3070
---
G
5
208-230*
3
17.1
85.0
25
30
---
240
376
590
920
H
5
380-415
3
8.8
38.0
15
15
472
750
1173
1841
2867
F
5
575
3
7.0
36.0
15
15
929
1477
2311
3627
---
J
*Figures represent maximum length in feet for 220 or 230 volt system. Use 75% of length for 208 volt system.
rj/051-301-11.eps
4.0" Approx.
3" NPT male
thread
Pump
Veeder-Root only supplies
the adapter.
Red Jacket pumps are
centrifugal type and as
such are not designed to
pump product when level
is below the bottom of the
pump.
Before installing pipe
threads apply an adequate
amount of fresh, UL
classified for petroleum,
non-setting thread sealant.
1.
2.
3.
NOTES