Introduction
Warnings and Instructions
6
In addition to the specified torque values noted in this manual, when properly tightened, all flanged fittings should
have metal-to-metal contact.
Warnings and Instructions
This section introduces the hazards and safety precautions associated with
installing, inspecting, maintaining or servicing this product. Before
performing any task on this product, read this safety information and the
applicable sections in this manual, where additional hazards and safety
precautions for your task will be found. Fire, explosion, electrical shock or
pressure release could occur and cause damage to property, environment,
resulting in serious injury or death, if these safe service procedures are not
followed.
PRELIMINARY PRECAUTIONS
You are working in a potentially dangerous environment of flammable fuels,
vapors, and high voltage or pressures. Only trained or authorized individuals
knowledgeable in the related procedures should install, inspect, maintain or
service this equipment.
Read the Manual
Read, understand and follow this manual and any other labels or related materials supplied with this equipment. If
you do not understand a procedure, call 1-800-323-1719 to locate a qualified technician. It is imperative to your
safety and the safety of others to understand the procedures before beginning work.
Make sure your
employees and any service contractors read and follow the instructions.
WARNING
This product operates in the highly combustible atmosphere of a diesel storage
tank.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT,
RESULTING IN SERIOUS INJURY OR DEATH.
1. All installation work must comply with the latest issue of the National
Electrical Code (NFPA 70), the Code for Motor Fuel Dispensing Facilities and
Repair Garages (NFPA 30A), and any European, national, state, and local code
requirements that apply.
2. If an E-stop is required by national or local codes or a local authority having
jurisdiction, the HydrX Fuel Conditioning Controller (FCC) power must be
supplied by a 15 amp circuit that can be interrupted by the same E-Stop as the
FCC pump. Both the hot and neutral legs of the PLC must be connected to the
E-Stop.
3. Turn off, tag, and lockout power to the STP before connecting or servicing the
STP.
4. Before installing pipe threads apply an adequate amount of fresh, UL
classified for petroleum, non-setting thread sealant. For AG applications,
Loctite 564 is recommended for all field serviceable pipe threads.
5. To protect yourself and others from serious injury, death, or substantial
property damage, carefully read and follow all warnings and instructions in
this manual.