4
Vac System Testing - TLS-350/350R Consoles
Vac Sensor Setup
4-4
PERFORMING VAC SENSOR SETUP
After filling in the Vac Sensor Zone Worksheet, enter the Setup Mode and press the FUNCTION key until you see
the message:
Press STEP until you see the message:
Following the completed Vac Sensor Zone Worksheet, configure each Vac Sensor channel for all SmartSensor
modules. NOTE: Once the console communicates with a Vac Sensor (approximately 2 minutes after configuration),
it automatically selects the Vac Sensor SS Category for that sensor.
When all Vac Sensors have been configured, if necessary, press Tank/Sensor until you see the message:
Press ENTER:
You must select the pump that will provide the source of vacuum for this Vac Sensor or a Setup Data Warning will
be posted for this Vac Sensor. If necessary, press CHANGE until the correct pump’s control device displays [QX
(PLLD), WX (WPLLD), or RX (Output Relay)]. NOTE: an Output Relay must be set to Pump Control Output to be
assigned as a pump. If the selected pump output relay is not assigned to a pump sense device, a Setup Data
Warning for this Vac Sensor will be posted.
Press ENTER to confirm your entry. Press STEP to continue:
Referring to your previously completed volume worksheet, enter the volume in gallons of the interstitial space being
monitored by this Vac Sensor. The permitted range is 0.1 to 500 gallons (0.378 to 1892.7 litres). Default is 501
(1896.4 Litres). A Setup Data Warning alarm will activate if a volume between 0.1 and 500 is not entered.
Press CHANGE and enter the interstitial space volume. Press ENTER to confirm your entry.
Press STEP to continue:
For all Vac Sensors except the one monitoring a fiberglass tank’s interstitial space, a relief valve is usually not
needed. For Vac Sensors not requiring a relief valve press STEP to accept the default NO. Press Tank/Sensor to
setup another Vac Sensor.
For the Vac Sensor that monitors a fiberglass tank’s interstitial space, a relief valve is required to prevent excess
vacuum from damaging the tank. Press CHANGE and select YES. Press ENTER to confirm your entry.
Press STEP to continue.:
SMARTSENSOR SETUP
PRESS <STEP> TO CONTINUE
SS CONFIG - MODULE 1
SLOT
x
- X X X X X X X X
s
1: VAC SENSOR SETUP
PRESS <ENTER>
s
1: SELECT PUMP #
NONE
s 1: (Vacuum Label)
VOLUME:
501
s 1: (Vacuum Label)
RELIEF VALVE: NO
s 1: (Vacuum Label)
RELIEF VALVE PRESSURE: -9.0