Vac System Testing - TLS-350/350R Consoles
This section describes a sequence of procedures and tests necessary to complete the Vac Sensor installation:
1. ATM Pressure Sensor setup
2. Vac Sensor setup
3. Vacuum integrity test prior to filling tank
*
4. Manual test
*
5. Operability test
*
Only one of these two tests is required to complete the installation.
ATM Pressure Sensor Setup
The ATM Pressure Sensor is factory installed in the Smart Sensor / Press module and preassigned to channel 8.
At least one Smart Sensor / Press module, which contains the ATM Pressure Sensor, must be installed in the
console. You must configure at least one ATM Pressure Sensor for use by the Vac Sensors or a Setup Data
Warning will occur. NOTE: if more than one Smart Sensor / Press module is installed, only one ATM Pressure
Sensor needs to be configured.
Look in console and note the slot position of the SmartSensor / Press module. Enter the Setup Mode and press
the FUNCTION key until you see the message:
Press STEP until you see the message:
Where
x
is the slot number containing the SmartSensor / Press module. Press the
key to move the cursor to the
last (8th) X. Press CHANGE and the message below should appear:
Press STEP:
NOTE: In the example above, the ATM P sensor position is 8 but it could be16, 24, 32, or 40 depending on the
Smart Sensor's module number.
Press CHANGE and enter a label:
SMARTSENSOR SETUP
PRESS <STEP> TO CONTINUE
SS CONFIG - MODULE
n
SLOT
x
- X X X X X X X X
SLOT
x
- X X X X X X X 8
PRESS <STEP> TO CONTINUE
ENTER SMARTSENSOR LABEL
s 8:
ENTER SMARTSENSOR LABEL
s 8: (ATMP Sensor Label)