background image

 

Thermostat TOA

 

 

Doc: 70-00-0851A V1.0, 20210716 

© Vector Controls GmbH, Switzerland 

 Page 2 / 10 

Subject to change without notice 

www.vectorcontrols.com 

Types and Ordering 

Product Name 

Product No.  Description / Configuration 

Option 

Thermostat

 

TOA-T101 

40-100242 

230 VAC or 24V AC/DC power supply 

24 V AC/DC output voltage 

 

TOA-T102 

40-100243 

230 VAC power supply and output voltage 

 

Temperature Sensor not included / order separately (any Sxx-Tn10 type can be used)

 

S-Tn10-005-A 

40-200210 

Temperature sensor (for measuring at the thermostat) 

5 cm, PVC-cable 

SOD-Tn10-1 

40-200211 

Temperature sensor 

1 m, PVC-cable 

Accessories 

OPA-S 

40-500006 

External display and operation terminal with LCD display and 4 

keys 

 

AEC-PM2 

40-500130 

Memory device for easy copying of settings 

 

 

Safety 

 

DANGER! Safety advice 

This device is for use as a temperature control unit. It is not a safety device. Where a device failure could 

endanger human life and property, it is the responsibility of the client, installer and system designer to add 

additional safety devices to prevent system failure. Ignoring specifications and local regulations may cause 

equipment damage and endangers life and property. Tampering with the device and misapplication will void 

warranty. 

 

Technical Specifications 

Power supply 

Operating voltage: TOA-T101 

230 VAC, ± 10 %, 50/60 Hz 

24 VAC, ± 10 %, 50/60 Hz  

24 VDC, 15…34 VDC

 

 

TOA-T102 

230 VAC, ± 10 %, 50/60 Hz 

Power consumption 

Min.10 VA 

Safety extra low voltage (SELV) 

HD 384, Class II 

Electrical connection 

Screw terminals, cable 2x 0.34

…2.5mm²

 (

AWG 22…14)

 

Outputs 

Switching logic 

Relay, normally closed 

Output voltage:   TOA-T101 

 

If powered with 230 VAC: 24 VAC 

If powered with 24 V AC/DC: 24 V AC/DC  

 

TOA-T102 

230 VAC 

Output power:  

TOA-T101 

 

If powered with 230 VAC: 5 VA 

If powered with 24 V AC/DC: according power supply 

 

TOA-T102 

According power supply 

Relay output: SPST (NO) 

2 A Full load current 

Insulation strength

 

4000 VAC between relays and system electronics

 

1000 VAC between neighboring contacts

 

Electrical connection 

Screw terminal, cable 2x 0.34

…2.5mm²

 

(AWG 22…14)

 

Inputs 

Type 

External temperature sensor: Sxx-Tn10 (

NTC 10kΩ@25°C

Range 

-

20…100 °C (

-

4…212 °F)

 

Accuracy 

0.5°C at 

0…50 °C

 

(32…122 °F)

 

1.0°C at -

20…0 °C

 (-

4…32 °F)

 

/ 50…100 °C

 

(122…212 °F)

 

Environment 

Operation 

Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 

Class 3K5 

0...50 °C (32...122 °F) 

< 95 % RH non-condensing 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

Class 3K3 und class 1K3 

-25...70 °C (-13...158 °F) 

< 95 % RH non-condensing 

Class 2MT2 

Standards 

Degree of protection 

IP40 (EN 60529)  

Overvoltage category 

III (EN 60730-1) 

Safety class 

II (IEC 60536) 

Environmental class 

II (EN 60730-1) 

 

 

Содержание TOA-T101

Страница 1: ...limits 20 100 C 4 212 F adjustment range 0 5 C 1 F measuring accuracy Signal LED indicates operating status of Thermostat Temperature can be measured at the device or remotely Easy programming of set...

Страница 2: ...ty Technical Specifications Power supply Operating voltage TOA T101 230 VAC 10 50 60 Hz 24 VAC 10 50 60 Hz 24 VDC 15 34 VDC TOA T102 230 VAC 10 50 60 Hz Power consumption Min 10 VA Safety extra low vo...

Страница 3: ...sions mm inch Mounting and Installation The Thermostat must be mounted on a dry place Temperature sensor selection Use Vector Controls NTC temperature sensors to achieve maximum monitoring accuracy Di...

Страница 4: ...y 230 VAC 50 60 Hz P3 Input Power supply 24 V AC DC P4 Input Temperature sensor NTC 10k at 25 C P6 Connection for OPA S operation terminal Plug P7 Connection for AEC PM2 memory device Plug J1 Connecto...

Страница 5: ...Power supply 230 VAC 50 60 Hz P4 Input Temperature sensor NTC 10k at 25 C P6 Connection for OPA S operation terminal Plug P7 Connection for AEC PM2 memory device Plug LED Signal LED shows operating st...

Страница 6: ...see picture below 4 Close unused housing cable cut out with the supplied blind insert see picture below 5 Apply operating voltage to TOA and observe signal LED see section Signal LED page 7 The signa...

Страница 7: ...ltage for an OFF ON setting of 20 C 25 C 68 F 77 F Signal LED The signal LED on the top of the housing indicates the operating status of the TOA LED Status Description red Output is off The contact is...

Страница 8: ...T key 5 Confirm the IP SEL display with the RIGHT key The first parameter is displayed 6 Change to the parameter IP 03 with the UP or DOWN keys After pressing the RIGHT key the parameter Switching OFF...

Страница 9: ...s set to 7 9 Remove the AEC PM2 memory device and the OPA S operator interface and close the TOA housing see section Connecting the TOA and putting it into operation page 6 Copy parameters to other TO...

Страница 10: ...ector Controls GmbH Switzerland Page 10 10 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland...

Отзывы: