background image

 

SDC-C1 

D

UCT 

CO2

 

T

RANSMITTER

 

 

Doc: 70-00-0399A, V2.9, 20220405  

© Vector Controls GmbH, Switzerland  

Page 5-8 

Subject to change without notice  

www.vectorcontrols.com 

Configuration 

Output signal configuration, Jumper settings 

The analog output signal type for the AO1 output may be configured with jumper 

JP1

 for Voltage or Current control signals. The factory setting is Voltage. 

 

For Jumper location see section 

Wiring and Connection

 on page 

3. 

 
The signal range may be set with jumper 

JP4

 for the analog signal output AO1. 

JP4

 will only operate if the output range specified with output parameter 

OP 01

 

and 

OP 02

 is left at the default value 

of 0…100%. 

With any other setting the 

position of 

JP4

 has no influence and the signal range defined with the output 

parameters 

OP 01

 and 

OP 02 

applies. 

 

For Jumper location see section 

Wiring and Connection

 on page 

3. 

Parameter configuration 

The transmitter can be adapted to fit perfectly into any application by adjusting the software parameters. The parameters 

are set with the operation terminals OPA-S or the optional bult-in OPC-S. The OPA-S may also be used as remote 

indicator. 

 

NOTE: For the correct display of data, version 1.7 or grater of OPA-S is required. 

 

OPA-S operation 

1.

 

Open SDC housing (see SDC-C1 installation sheet no. 70-00-0573 

http://www.vectorcontrols.com/

). 

2.

 

Connect the OPA-S operating device to the OPA-S connector on the SDC (see section 

Wiring and Connection

 on 

page 3). The measured CO2 value is displayed. 

3.

 

Press the "Up" and "Down" keys simultaneously for more than 3 seconds. "Code 0000" is displayed. 

4.

 

Use the "UP" and "DOWN" keys to set the password "0009" and confirm with the "RIGHT" key. 

5.

 

Select "IP SEL 

(Input Parameter) or “OP SEL” (Output Parameter) with 

"UP" and "DOWN" and confirm with the 

"RIGHT" key. The first parameter is displayed. 

6.

 

Use the "UP" and "DOWN" key to switch to the desired parameter. After pressing the "RIGHT" key adjust the 

parameter value with the "UP" and "DOWN" keys. Confirm the setting with the "RIGHT" key. 

7.

 

Complete parameter setting by pressing the left "ON/OFF" key twice. The measured CO2 value is displayed. 

 

 

Important 

In order for the SDC-C1 to apply the new settings correctly, the parameter setting must be completed with the 

left "ON/OFF" key! 

 

 

Detailed information on the OPA-S can be found on the websit

www.vectorcontrols.com

 on the corresponding 

product page under "Downloads". 

 

OPC-S operation 

1.

 

Press the "Up" and "Down" keys simultaneously for more than 3 seconds. "Code 0000" is displayed. 

2.

 

Use the "UP" and "DOWN" keys to set the password "0009" and confirm with the "RIGHT" key. 

3.

 

Select "IP SEL 

(Input Parameter) or “OP SEL” (Output Parameter) with 

"UP" and "DOWN" and confirm with the 

"RIGHT" key. The first parameter is displayed. 

4.

 

Use the "UP" and "DOWN" key to switch to the desired parameter. After pressing the "RIGHT" key adjust the 
parameter value with the "UP" and "DOWN" keys. Confirm the setting with the "RIGHT" key. 

5.

 

Complete parameter setting by pressing the left "ON/OFF" key twice. The measured CO2 value is displayed. 

 

 

Important 

In order for the SDC-C1 to apply the new settings correctly, the parameter setting must be completed with the 

left "ON/OFF" key! 

 

 

Detailed information on the OPC-S can be found on the websit

www.vectorcontrols.com

 on the corresponding 

product page under "Downloads". 

 

 

 

Signal type 

JP1 

Voltage (VDC) 

 

Current (mA) 

 

Signal range 

JP4 

0

10 V, 0

20 mA 

 

2

10 V, 4

20 mA 

 

Содержание SDC-C1

Страница 1: ...er to reach the given accuracy it is required that the sensor is for at least 3 weeks in operation NOTE The ABC calibration works only in those applications where the CO2 concentration sinks regularly...

Страница 2: ...tputs Analog outputs Output signal Resolution Maximum load 0 10 VDC 0 20 mA or 2 10 VDC 4 20 mA 10 bit 9 7 mV 0 019 5 mA Voltage signal 1k current signal 250 Environment Operation Climatic conditions...

Страница 3: ...ion on page 5 Mounting instruction See SDC C1 installation sheet no 70 000573 www vectorcontrols com Dimension mm inch 2 10V 4 20mA 0 10V 0 20mA Range STATUS LED OPA S VDC mA AO1 JP4 JP1 OPC S Sensor...

Страница 4: ...the UP key for at least 5 seconds and wait until the value changes Use of OPC S 1 Press the UP key to see the maximum values or the DOWN key to see the minimum values 2 To reset the minimum value pre...

Страница 5: ...he UP and DOWN keys to set the password 0009 and confirm with the RIGHT key 5 Select IP SEL Input Parameter or OP SEL Output Parameter with UP and DOWN and confirm with the RIGHT key The first paramet...

Страница 6: ...ameter Description Range Default OP 00 AO1 CO2 Configuration of output signal 0 CO2 value 1 Recorded minimum CO2 value 2 Recorded maximum CO2 value 0 2 0 OP 01 AO1 CO2 Minimum limitation of CO2 output...

Страница 7: ...r level of CO2 could prevent a stable signal Observe the CO2 value on the OPA S 2 Once the CO2 value has stabilized login with the OPA S and set IP 06 2 then exit configuration mode The air quality le...

Страница 8: ...20405 Vector Controls GmbH Switzerland Page 8 8 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzer...

Отзывы: